Plan Review Notes
Plan Review Notes For Permit 08030723
Permit Number 08030723
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-08 17:13:35** DENIED2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS WHICH
 ARE BASED ON REVISED PLANS OR INFORMATION NOW BEING
 SHOWN.
 ** PLEASE ALSO SEE THERE IS A NEW COMMENT WHICH WAS NOT
 ON PREVIOUS REVIEW EVEN AS PREVIOUS PLANS DID CONTAIN
 ERROR.
  
 1) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 .1.3 AND
 13-415.2. PLEASE KNOW ALLOWANCES FOR ADDITIONAL
 LIGHTING IN AREAS MAY NOT BE USED OR TAKEN INTO ACCOUNT
 IN CALCULATIONS UNLESS SPECIFICALLY INSTALLING LIGHTING
 ETC FOR THAT ADDITIONAL ALLOWANCE.
  
 FOR EXAMPLE:
 PLEASE SEE THE HALLWAY AREAS OUTSIDE THE BATHROOMS
 WHICH ARE TAKING AN ADDITIONAL 1W PER SQ FT FOR
 DECORATIVE LIGHTING YET NONE OF THESE TYPES OF FIXTURES
 ARE ON PLANS.
 ** THIS IS ONE EXAMPLE GIVEN. THIS IS NOT THE ONLY
 LOCATION. BASED ON THE ALLOWANCES PERMITTED IN THE CODE
 AND THE DESIGN WATTAGE TOTAL SHOWN THE TOTAL DESIGN
 WATTAGE IS OVER.
 PLEASE ADJUST.
 ** NOTED PREVIOUSLY
  
 2) NOTE: PLEASE SHOW THE SHOW WINDOW CALCULATIONS PER
 220.43A.
 ** AN EXAMPLE OF THIS IS CIRCUIT LA-1 WHICH SHOWS A 1.0
 KVA. HOW IS THIS POSSIBLE WHEN THE LINEAR FT OF WINDOW
 IS 13FT AND THE CODE REQUIRES A LOAD OF 200VA PER FT.
 THE LOAD FOR BRANCH CIRCUIT SIZING PER 220.14 AND
 SIZING FOR SERVICE PER 220.43 IS NOT THE SAME.
 PLEASE SHOW THESE FIGURES INTO REVISED LOAD
 CALCULATIONS FOR PANELS AND SERVICE.
 ** NOTED PREVIOUSLY
  
 3) NOTE: PLEASE SEE SECTION 220.43B FOR TRACK LIGHTING
 AND SHOW LOAD IN CALCULATIONS FOR PANELS AND SERVICE.
 ** NOTED PREVIOUSLY.
  
 4) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTS. BASED ON PLANS, FLOOR LAYOUT AND DESIGN MAY NOT
 USE EXCEPTION AND MUST CIRCUIT TO THE LOCAL LIGHTING
 BRANCH CIRCUIT IN ANY ONE AREA AHEAD OF ANY SWITCHING
 DEVICES INCLUDING LIGHTING CONTROL PANEL.
 ** THIS IS A NEW COMMENT EVEN THOUGH PLANS DO CONTAIN A
 NOTE #2 WHICH IS LABELED TO CONNECT AHEAD OF LOCAL
 CIRCUIT. AS THE PLANS SHOW THESE EMERGENCY LIGHT
 FIXTURES TO THEIR OWN CIRCUIT ON THE LIGHTING CONTROL
 PANEL AND TO EACH LOCAL CIRCUIT BY NOTE, THESE NEEDS TO
 BE ADDRESSED AND COORDINATED.
  
 5) NOTE: PLEASE COORDINATE THE FEEDERS FOR LIGHTING
 PANEL. RISER SHOWS A NOTE *D* WHICH NOTES #3 CONDUCTORS
 YET THE PANEL SCHEDULE RISER AND PANEL SCHEDULE *LB*
 STATES #6 FOR THE SAME FEEDERS.
 THIS IS A NEW COMMENT AS THE PREVIOUS PLANS SHOWED THE
 SAME.
 PLEASE COORDINATE. 310.16, 240.4, 408.4
 FBC 106.1.2, 106.1.1 FOR COORDINATION AND CLARITY OF
 PLANS.
 ** NEW COMMENT MISSED FROM NOTES IN PREVIOUS REVIEW.
  
 6) NOTE: PLEASE COMPLETE BAY NUMERICAL DESIGNATIONS ON
 POWER PLANS FOR COORDINATION OF CIRCUITING WITH PANEL
 SCHEDULES.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF RECORD
 PLANS.
 ** NOTED ON PREVIOUS REVIEW
  
 7) NOTE: PLEASE VERIFY ANY EXTERIOR LIGHTING AT THIS
 LOCATION. PLANS, PANELS, LOAD CALCULATIONS ETC DO NOT
 INDICATE ANY LIGHTING.
 SITE/SURVEY DOES INDICATE EXTERIOR LIGHTS SUCH AS LIGHT
 POLES HOWEVER NONE INCLUDED AS NOTED.
 PLEASE COMPLETE AND COORDINATE ALL ITEMS SUCH AS
 LIGHTING CONTROLS PER 13-415.1.ABC.1.4, LOADS PER NEC
 220, PANEL SCHEDULES PER NEC 408, CIRCUITING,
 CONDUCTORS BREAKERS ETC.
 ** THIS IS NEW BASED ON REVISED PLANS NOWSHOWING
 EXTERIOR LIGHTINGWHICH WAS NOT ON PREVIOUS PLANS.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]