| 2008-07-08 17:13:35 | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | ** PLEASE ALSO SEE THERE ARE SOME NEW COMMENTS WHICH |
| | ARE BASED ON REVISED PLANS OR INFORMATION NOW BEING |
| | SHOWN. |
| | ** PLEASE ALSO SEE THERE IS A NEW COMMENT WHICH WAS NOT |
| | ON PREVIOUS REVIEW EVEN AS PREVIOUS PLANS DID CONTAIN |
| | ERROR. |
| | |
| | 1) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2 .1.3 AND |
| | 13-415.2. PLEASE KNOW ALLOWANCES FOR ADDITIONAL |
| | LIGHTING IN AREAS MAY NOT BE USED OR TAKEN INTO ACCOUNT |
| | IN CALCULATIONS UNLESS SPECIFICALLY INSTALLING LIGHTING |
| | ETC FOR THAT ADDITIONAL ALLOWANCE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE HALLWAY AREAS OUTSIDE THE BATHROOMS |
| | WHICH ARE TAKING AN ADDITIONAL 1W PER SQ FT FOR |
| | DECORATIVE LIGHTING YET NONE OF THESE TYPES OF FIXTURES |
| | ARE ON PLANS. |
| | ** THIS IS ONE EXAMPLE GIVEN. THIS IS NOT THE ONLY |
| | LOCATION. BASED ON THE ALLOWANCES PERMITTED IN THE CODE |
| | AND THE DESIGN WATTAGE TOTAL SHOWN THE TOTAL DESIGN |
| | WATTAGE IS OVER. |
| | PLEASE ADJUST. |
| | ** NOTED PREVIOUSLY |
| | |
| | 2) NOTE: PLEASE SHOW THE SHOW WINDOW CALCULATIONS PER |
| | 220.43A. |
| | ** AN EXAMPLE OF THIS IS CIRCUIT LA-1 WHICH SHOWS A 1.0 |
| | KVA. HOW IS THIS POSSIBLE WHEN THE LINEAR FT OF WINDOW |
| | IS 13FT AND THE CODE REQUIRES A LOAD OF 200VA PER FT. |
| | THE LOAD FOR BRANCH CIRCUIT SIZING PER 220.14 AND |
| | SIZING FOR SERVICE PER 220.43 IS NOT THE SAME. |
| | PLEASE SHOW THESE FIGURES INTO REVISED LOAD |
| | CALCULATIONS FOR PANELS AND SERVICE. |
| | ** NOTED PREVIOUSLY |
| | |
| | 3) NOTE: PLEASE SEE SECTION 220.43B FOR TRACK LIGHTING |
| | AND SHOW LOAD IN CALCULATIONS FOR PANELS AND SERVICE. |
| | ** NOTED PREVIOUSLY. |
| | |
| | 4) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| | LIGHTS. BASED ON PLANS, FLOOR LAYOUT AND DESIGN MAY NOT |
| | USE EXCEPTION AND MUST CIRCUIT TO THE LOCAL LIGHTING |
| | BRANCH CIRCUIT IN ANY ONE AREA AHEAD OF ANY SWITCHING |
| | DEVICES INCLUDING LIGHTING CONTROL PANEL. |
| | ** THIS IS A NEW COMMENT EVEN THOUGH PLANS DO CONTAIN A |
| | NOTE #2 WHICH IS LABELED TO CONNECT AHEAD OF LOCAL |
| | CIRCUIT. AS THE PLANS SHOW THESE EMERGENCY LIGHT |
| | FIXTURES TO THEIR OWN CIRCUIT ON THE LIGHTING CONTROL |
| | PANEL AND TO EACH LOCAL CIRCUIT BY NOTE, THESE NEEDS TO |
| | BE ADDRESSED AND COORDINATED. |
| | |
| | 5) NOTE: PLEASE COORDINATE THE FEEDERS FOR LIGHTING |
| | PANEL. RISER SHOWS A NOTE *D* WHICH NOTES #3 CONDUCTORS |
| | YET THE PANEL SCHEDULE RISER AND PANEL SCHEDULE *LB* |
| | STATES #6 FOR THE SAME FEEDERS. |
| | THIS IS A NEW COMMENT AS THE PREVIOUS PLANS SHOWED THE |
| | SAME. |
| | PLEASE COORDINATE. 310.16, 240.4, 408.4 |
| | FBC 106.1.2, 106.1.1 FOR COORDINATION AND CLARITY OF |
| | PLANS. |
| | ** NEW COMMENT MISSED FROM NOTES IN PREVIOUS REVIEW. |
| | |
| | 6) NOTE: PLEASE COMPLETE BAY NUMERICAL DESIGNATIONS ON |
| | POWER PLANS FOR COORDINATION OF CIRCUITING WITH PANEL |
| | SCHEDULES. |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION OF RECORD |
| | PLANS. |
| | ** NOTED ON PREVIOUS REVIEW |
| | |
| | 7) NOTE: PLEASE VERIFY ANY EXTERIOR LIGHTING AT THIS |
| | LOCATION. PLANS, PANELS, LOAD CALCULATIONS ETC DO NOT |
| | INDICATE ANY LIGHTING. |
| | SITE/SURVEY DOES INDICATE EXTERIOR LIGHTS SUCH AS LIGHT |
| | POLES HOWEVER NONE INCLUDED AS NOTED. |
| | PLEASE COMPLETE AND COORDINATE ALL ITEMS SUCH AS |
| | LIGHTING CONTROLS PER 13-415.1.ABC.1.4, LOADS PER NEC |
| | 220, PANEL SCHEDULES PER NEC 408, CIRCUITING, |
| | CONDUCTORS BREAKERS ETC. |
| | ** THIS IS NEW BASED ON REVISED PLANS NOWSHOWING |
| | EXTERIOR LIGHTINGWHICH WAS NOT ON PREVIOUS PLANS. |
| | |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |