| Plan Review Notes For Permit 08030723 |
| Permit Number |
08030723 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-12 11:38:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8" | | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG | | | 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE | | | CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT | | | DIMENSION TO THE CENTERLINE OF THE W/C'S. | | | | | | 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH | | | SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. | | | | | | 3. SHT P-4 ELECTRIC WATER HEATER DETAIL. SHOW | | | COMPLIANCE WITH SECTION 607.3.2 THERMAL EXPANSION | | | CONTROL. INDICATE METHOD. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|