Plan Review Notes
Plan Review Notes For Permit 08030723
Permit Number 08030723
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-12 11:38:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3 DETAIL D-1 INDICATES THE W/C'S TO BE 1'8"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER FIG
 11-28 THE W/C'S SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. PLEASE SHOW CORRECT
 DIMENSION TO THE CENTERLINE OF THE W/C'S.
  
 2. SHT A-3 DETAIL D-2 PLEASE SHOW COMPLIANCE WITH
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 3. SHT P-4 ELECTRIC WATER HEATER DETAIL. SHOW
 COMPLIANCE WITH SECTION 607.3.2 THERMAL EXPANSION
 CONTROL. INDICATE METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  