2008-04-24 16:54:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS AND RESUBMIT:
  
 1. ELECTRICAL ROOM IS SHOWN ON PG A-1 TO BE ENCLOSED IN
 2-HOUR FIRE RESISTANCE RATED CONSTRUCTION. HVAC PLAN
 SHOWS A 6 INCH ROUND DUCT PENETRATING THE 2-HOUR WALL.
 SHOW HOW THIS DUCT PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.2 AND FBCM 607.8.
  
 2. HVAC PLAN NOTES CALL FOR ADJUSTABLE FRESH AIR
 INTAKE. MOTORIZED SHUTOFF DAMPER CONTROLS ARE REQUIRED
 FOR OUTDOOR AIR INTAKES IN ACCORDANCE WITH FBCEB 611.1
 AND FBCB 13-409.1.ABC.3.3.
  
 3. SUPPLY DUCT AND GRILL SERVING JANITOR?S CLOSET IS
 MISSING DUCT SIZE, CFM AND GRILL DESIGNATION. PROVIDE
 MISSING INFORMATION. FBCM 603.1, FBCB 106.1.1.
  
 4. PLAN IS NOT CLEAR AS TO WHETHER THE DUCT SHOWN ON
 PLANS IS TO BE ABOVE A CEILING OR EXPOSED BELOW THE
 CEILING. PLEASE CLARIFY. THIS INFORMATION AS WELL AS
 ADDITIONAL INFORMATION IS REQUIRED TO DEMONSTRATE
 ENERGY CODE COMPLIANCE FOR THE AIR DISTRIBUTION SYSTEM.
 SEE THE FOLLOWING SECTIONS: FBCB 13-410.1.ABC.2 AND
 13-410.1.ACB.3.
  