| 2008-04-04 11:01:31 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING MINIMUM CODES. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1.1.2 AND .1.3 FOR |
| | THE FOLLOWING ITEMS NEEDED. |
| | PLEASE PROVIDE MAXIMUM OVER RIDE TIMES FOR DEVICES. |
| | PLEASE SEE THAT WHEN OVER RIDES ARE LOCATED IN ANY |
| | BUILDING/SPACE THE OCCUPANT IS REQUIRED TO SEE ALL |
| | LIGHTING IN WHICH THEY ARE OVER RIDING OR MUST PROVIDE |
| | FOR THE EXCEPTION IN THE CODE. THE LOCATION ON PLANS |
| | DOES NOT PERMIT THE OCCUPANT TO SEE ALLLIGHTING AND |
| | NO INDICATORS AS REQUIRED COULD BE FOUND ON LIGHTING |
| | CONTROL RISER OR PLANS. |
| | |
| | 3) NOTE: PLEASE PROVIDE COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. |
| | PLEASE SEE 13-400.3.B, 13-400.3.C, ETC. |
| | AS NO LIGHTING PERFORMANCE CALCULATIONS WERE SUBMITTED |
| | A REVIEW OF THESE COULD NOT BE DONE AT THIS TIME. |
| | PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH |
| | THE CALCULATIONS TO BE PROVIDED. |
| | |
| | 4) NOTE: PLEASE SEE 600.5 FOR MISSING REQUIRED SIGN |
| | CIRCUIT. (PLEASE BE SURE TO ADD DEDICATED MINIMUM |
| | LOAD) |
| | |
| | 5) NOTE: PLEASE VERIFY ALL REQUIRED CONTINUOUS LOADS. |
| | PANEL LB STATES CONTINUOUS LOADS WERE FIGURED AT 125%, |
| | HOWEVER PANEL LA DOES NOT SHOW OR INDICATE THESE |
| | REQUIRED CONTINUOUS LOADS, |
| | FOR EXAMPLE; |
| | LIGHTING, WATER HEATER, ETC. |
| | 215.3, 230.42, 422.13 (2005 NEC) ETC. |
| | PLEASE ADJUST AND SHOW WHERE LOADS ARE FIGURED IN |
| | CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE SEE 220.43 AND PROVIDE LOADS ON SHOW |
| | WINDOWS AND HOW THEY WERE FIGURED INTO CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS |
| | ON ELECTRICAL PLANS. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE CLARIFY THE SIZES OF THE PANELS AS |
| | THESE ARE SHOWN AS 125AMPS WITH 42CIRCUITS ON ONE AND |
| | THE OTHER AS 200AMP AND 24 CIRCUITS. |
| | PLEASE SEE 110.3, 90.7 AND VERIFY LISTING OF THIS. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-04-03 19:06:59 | 2008-04-03 19:06:59 |
| | |
| | IN ELECTRICAL FOR REVIEW. |