Plan Review Notes
Plan Review Notes For Permit 08030723
Permit Number 08030723
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-04 11:01:31** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING MINIMUM CODES.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1.1.2 AND .1.3 FOR
 THE FOLLOWING ITEMS NEEDED.
 PLEASE PROVIDE MAXIMUM OVER RIDE TIMES FOR DEVICES.
 PLEASE SEE THAT WHEN OVER RIDES ARE LOCATED IN ANY
 BUILDING/SPACE THE OCCUPANT IS REQUIRED TO SEE ALL
 LIGHTING IN WHICH THEY ARE OVER RIDING OR MUST PROVIDE
 FOR THE EXCEPTION IN THE CODE. THE LOCATION ON PLANS
 DOES NOT PERMIT THE OCCUPANT TO SEE ALLLIGHTING AND
 NO INDICATORS AS REQUIRED COULD BE FOUND ON LIGHTING
 CONTROL RISER OR PLANS.
  
 3) NOTE: PLEASE PROVIDE COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SEE 13-400.3.B, 13-400.3.C, ETC.
 AS NO LIGHTING PERFORMANCE CALCULATIONS WERE SUBMITTED
 A REVIEW OF THESE COULD NOT BE DONE AT THIS TIME.
 PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH
 THE CALCULATIONS TO BE PROVIDED.
  
 4) NOTE: PLEASE SEE 600.5 FOR MISSING REQUIRED SIGN
 CIRCUIT. (PLEASE BE SURE TO ADD DEDICATED MINIMUM
 LOAD)
  
 5) NOTE: PLEASE VERIFY ALL REQUIRED CONTINUOUS LOADS.
 PANEL LB STATES CONTINUOUS LOADS WERE FIGURED AT 125%,
 HOWEVER PANEL LA DOES NOT SHOW OR INDICATE THESE
 REQUIRED CONTINUOUS LOADS,
 FOR EXAMPLE;
 LIGHTING, WATER HEATER, ETC.
 215.3, 230.42, 422.13 (2005 NEC) ETC.
 PLEASE ADJUST AND SHOW WHERE LOADS ARE FIGURED IN
 CALCULATIONS.
  
 6) NOTE: PLEASE SEE 220.43 AND PROVIDE LOADS ON SHOW
 WINDOWS AND HOW THEY WERE FIGURED INTO CALCULATIONS.
  
 7) NOTE: PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS
 ON ELECTRICAL PLANS.
 FBC 106.1.2
  
 8) NOTE: PLEASE CLARIFY THE SIZES OF THE PANELS AS
 THESE ARE SHOWN AS 125AMPS WITH 42CIRCUITS ON ONE AND
 THE OTHER AS 200AMP AND 24 CIRCUITS.
 PLEASE SEE 110.3, 90.7 AND VERIFY LISTING OF THIS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-04-03 19:06:592008-04-03 19:06:59
  
 IN ELECTRICAL FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved