2008-04-17 11:01:22BUILDING PLAN REVIEW
 PERMIT: 08030723
 ADD: 6910 S DIXIE HWY
 CONT: SULLIVAN BUILDERS
 TEL: (561)586-5353 (NEYITA)
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SHEET A-1 INDICATES TWO EXIT DOORS ONE ON EITHER
 SIDE OF THE BUILDING. BOTH EXIT DOORS INDICATE THE USE
 OF DOOR CLOSERS,AND WOULD HAVE SELF LATCHING
 DOORSBEING EXTERIOR EXIT DOORS.
 THE PLANS ARE MISSING THE REQUIRED 12" SIDE CLEARENCE
 ON THE LATCH SIDE OF THE DOOR, SEE11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 3) PRODUCT APPROVALS, PLEASE NOTE THAT THE TYPE OF
 GLAZING AND IF MULLIONS AND FRAMES REQUIRE REINFORCING,
 PLEASE SEE SHEET A-2 & S-1 THE WESTERN EXPOSURE,THE
 FRONT ENTRY IS DRAWN WITHOUT A TRANSOM BUT THE FRAMING
 MEMBERS OR BEAM THAT CARRIES THESE MEMBERS WOULD BE AT
 THE TALLEST WINDOWS. THE HORIZONTALL MULLION THAT WOULD
 BE CARRYING THE LOAD IS OVER 13'-6" LONG PLUS THE
 STUCCO LOADSAPPLIED TO THIS AREA. PLEASE VERIFY THE
 FRAMING CONDITIONS IN THIS AREA.AT THIS TIME UNABLE
 TO DO A REVIEW ON THE STOREFRONT PANEL WALL SYSTEM NOR
 DOORS DUE TO INSUFFICIENT INFORMATION.
 106.1.2 ADDITIONAL INFORMATION REQUIRED, & TABLE
 1609.2.1.(2).
  
 4) PLEASE PROVIDE ADDITIONAL INFORMATION, SHEET A-3
 INDICATES THE USE OF R-19 ICYNENE, THE USE OF ICYNENE
 TO THE UNDER SIDE OF THE ROOF SHEATHING DECK. THE PLANS
 DO NOT INDICATE IF THE
 END GABLE WALLS ARE A CONTINUATION OF THE CBS WALLS OR
 IF THEY ARE WOOD STUD GABLE END WALLS? THIS INFORMATION
 WILL HELPIN THE PLAN REVIEW. NOTE ALSO INCLUDED IS A
 ICC LEGACY REPORT NER-420
 AND A INFORMAL CODE INTERPRETATION.IF THE GABLE END
 WALLS ARE WOOD WALLS PLEASETAKE NOTE TO THE ASSEMBLY
 1-4 AND COMMENTS TO VERTICAL SURFACES AND
 REQUIREMENTS.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2.
  
 5)ADDITONAL INFORMATION REQUIRED, 106.1.2. SHEET A-3
 INDICATES THE USE OF 1/2" DRYWALL BUT THE FINISH IS NOT
 KNOWN. PLEASE LOOK AT TABLE 2508.1 FOR GYPSUM BOARD
 APPLICATIONS GA-216 IS REFERENCED. THE APPLICATION OF
 WATER BASED TEXTURE MATERIALS ISA CONCERN EXSPECIALLY
 ON A NON VENTED VEILING. PLEASE SEE TABLE 1 AND THE
 APPENDIX A.2FOR THE CONCERNS AND REQUIREMENTS FOR
 FRAMING SPACING.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved