| Plan Review Notes For Permit 08030721 |
| Permit Number |
08030721 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-23 12:27:12 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | 1} THERE IS A "220 GFI" SHOWN ON SHEET # 2, AND SHEET | | | #3 INDICATES A JUNCTION BOX. CLARIFY IF A DEVICE IS TO | | | BE INSTALLED OR CONDUCTORS ARE TO BE CAPPED OFF IN A | | | JUNCTION BOX. IN EITHER CASE NOTE COMPLIANCE WITH | | | 314.15.GIVE THE AMPERAGE RATING AND CONDUCTOR SIZE FOR | | | THE OUTLET | | | | | | 2} INDICATE IF THE "JACUZZI" ON SHEET #3 IS PORTABLE OR | | | BUILT IN. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | | AMENDED, TO INSTALL THE 240 VOLT LINE SHOWN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|