| Plan Review Notes For Permit 08030713 |
| Permit Number |
08030713 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-21 11:35:50 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1. ARCHITECTURAL QUALITY PLANS, DRAWN TO SCALE MINIMUM | | | 1/8IN, REQUIRED.PLANS ARE NOT TO SCALE AND DOES NOT | | | APPEAR TO BE GRAPHICALLY CORRECT. | | | | | | 2. SPACING OF JOISTS NOT CLEAR.PLEASE SPECIFY. | | | | | | 3. PLANS SHOW ANCHOR BASE, SPECIFY.PRODUCT APPROVAL | | | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. | | | | | | 4.THE PLAN SHOWS BOLT, SPECIFY SIZE (LENGTH, | | | DIAMETER). | | | | | | 5. SIDE VIEW SHOWS A 2X10, BUT THE PLAN SHOWS THIS AS | | | THE SAME SIZE AS 6X6 POSTS. ARE THE 2X10S ON TOP, ON | | | EACH SIDE? CLARIFY. | | | | | | 6. DECLARE WIND DESIGN CRITERIA, FBC301. | | | | | | 7. DECLARE GOVERNING CODE, INCLUDING 2007 | | | REVISIONS/SUPPLEMENTS. | | | | | | 8. TWO DIMENSIONS ARE SHOWN FOR THE FOOTINGS, 8X8, BUT | | | THERE SHOULD BE A THIRD DIMENSION (L X W X H). | | | | | | 9.SHOW HOW THE FOUR 8X8 FOOTINGS KEEP THE STRUCTURE | | | FROM OVERTURNING. | | | | | | 10. PROVIDE A LEGIBLE SITE PLAN WHICH DOES NOT HAVE THE | | | CITY STAMPS ON IT. |
|