Plan Review Notes
Plan Review Notes For Permit 08030710
Permit Number 08030710
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-10 11:13:49** PROVISO**
  
  
 1) NOTE:PLEASE SEE PANEL SCHEDULE IS SHOWING THE
 WASHER AND DRYER AS ONE CIRCUIT YET PLANS CLEARLY SHOW
 THESE AS TWO SEPARATE APPLIANCES.
 PLEASE INCLUDE REQUIRED DEDICATED CIRCUIT FOR WASHER
 AND REVISE PANEL SCHEDULE. 210.11C2.
  
 2) NOTE: PLEASE SEE SMOKE DETECTION DEVICES ARE TO BE
 SHOWN AS SA FOR SMOKE ALARMS UNLESS SYSTEM IS A LOW
 VOLTAGE FIRE ALARM SYSTEM WITH FIRE ALARM PANEL, HORNS
 ETC.
 NFPA-72
  
 3) NOTE: PLEASE VERIFY NEW OR EXISTING REAR OF DWELLING
 RECEPTACLE AS REQUIRED PER 210.52E. SHALL BE GFP AND
 WEATHER PROOF AS REQUIRED PER 210.8A3, 406.8B
  
  
 ** PLEASE REVISE PLANS WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  