Plan Review Notes
Plan Review Notes For Permit 08030710
Permit Number 08030710
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-07 11:18:07PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A2 SANITARY PLUMBING RISER: VENT REQUIRED FOR
 THE LAVATORY AND WATER CLOSET. PER FBC-2004 PLUMBING
 SECTION 901.1.2 VENTING REQUIRED.
  
 2. SHEET A2 SANITARY PLUMBING RISER: THE WASHING
 MACHINE MUST DRAIN DOWNSTREAM OF THE BATHROOM.PER
 FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 3. SHEET A2 SANITARY PLUMBING RISER: THE FOLLOWING IS
 REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 *WASHING MACHINE BRANCH DRAIN AND STACK SHALL BE 3".
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 *CLEARLY INDICATE THE REQUIRED STANDPIPE ON
 RESUBMITTED DRAWINGS.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 *CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 *CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT 4'
 A.F.F.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER