| 2008-04-01 12:51:41 | ** DENIED** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT A LAYOUT FOR REQUIRED SMOKE |
| | ALARMS FOR EXISTING MEETING CURRENT CODE OR FOR NEW TO |
| | BE INSTALLED. PLEASE SEE FBC R313, NFPA-72 11.5.1.1, |
| | 11.8.3. |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED |
| | ON PLANS. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 3) NOTE: PLEASE SEE 210.8A1, 210.52D AND 210.11C3 FOR |
| | MISSING BATHROOM CIRCUIT AND GFI. |
| | MUST BE 20AMP AND #12. |
| | |
| | 4) NOTE: PLEASE SEE THE RISER SHOWS A NEW ELECTRICAL |
| | SERVICE. PLEASE SUBMIT THE FOLLOWING: |
| | AIC RATING OF NEW MAIN. 110.9 |
| | EQUIPMENT GROUNDING CONDUCTOR MISSING FROM MAIN TO |
| | SUB-PANEL. 250.110, 250.122 ETC |
| | MINIMUM OF 20FT OF FOOTER STEEL NOT 9FT AS STATED ON |
| | PLANS. 250.50. |
| | LOCATION OF ALL EQUIPMENT, PANEL, DISCONNECT ETC. |
| | 240.24, 408.7, 110.26 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SUBMIT A PANEL SCHEDULE SHOWING THE |
| | EXISTING AND NEW CIRCUITS. |
| | 408.4, 240.4, 310.16 |
| | FBC 106.3.5.4 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |