2008-04-10 06:56:222004 FBC W/2007 REVISIONS
 R-3ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN THAT
 SPECIFIES THE DISTANCES FROM THE PROPOSED ADDITION TO
 THE PROPERTY LINES.
  
 4) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC
 13-600.
  
 5) THE MINIMUM INSULATION FOR 2 X 6 FRAME WALLS IS
 R-19. THE MINIMUM INSULATION FOR RAISED WOOD FLOORS IS
 R-11. REVISE WALL SECTION ON A1. SEE FBC 13-602 AND
 13-605.
  
 6) SPECIFY THE TERMITE TREATMENT THAT WILL BE USED ON
 THE PLAN AS REQUIRED BY FBC R320.1.
  
 7) SHOW COMPLIANCE WITH FBC R408.1 VENTILATION. THE
 UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR
 JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE
 OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED
 WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION
 OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH
 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF UNDER
 -FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING SHALL
 BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID
 BUILDING.
  
 8) SHOW COMPLIANCE WITH R408.3 ACCESS.
 ACCESS SHALL BE PROVIDED TO ALL UNDER -FLOOR SPACES.
 ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF
 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS
 THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24
 INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE
 THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT
 LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM)
 SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE
 BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL
 ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO
 THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS
 WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS.
  
 9) THE EXTERIOR WALL SECTION ON A1 DOES NOT APPEAR TO
 PROVIDE A SIX INCH CLEARANCE FOR TERMITE INSPECTION.
 SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 10) PROVIDE A DETAIL INDICATING THE ATTACHMENT OF THE
 NEW FOUNDATION AND FRAME WALLS TO THE EXISTING
 STRUCTURE.
  
 11) THE ATTIC VENTS SPECIFIED ON THE EXTERIOR WALL
 SECTION WILL HAVE TO BE CONTINUOUS IN ORDER TO PROVIDE
 VENTILATION TO THE SINGLE ASSEMBLY ROOF SYSTEM. SEE
 R806.1.
  
 12) SPECIFY THE WINDOW TYPE AND SIZE FOR THE LAUNDRY
 ROOM WINDOW. FBC 106.1.1* CITY AMENDMENTS.
  
 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING IN THE STEM WALL.
  
 14) SPECIFY THE SIZE OF THE HORIZONTAL REINFORCING IN
 THE BOND BEAM FOR THE STEM WALL.
  
 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE FRAME WALL TO THE FLOOR JOIST AS REQUIRED FOR A
 CONTINUOUS LOAD PATH. R301.1
  
 16) THE WALL SECTION ON A1 SPECIFIES 2 X 12 PT FLOOR
 JOISTS @ 16" OC WITH A 2 X 10 BAND. THE FLOOR FRAMING
 PLAN ON A1 SPECIFIES 2 X 10 JOISTS @ 16" OC. PLEASE
 CORRECT.
  
 17) THE INFORMATION ON THE DIAPHRAGM SCHEDULE ON A1
 CONFLICTS WITH THE NOTES ON THE EXTERIOR WALL SECTION
 FO THE ROOF AND WALL SHEATHING FASTENING.
  
 18) THE EXTERIOR WALL SECTION ON A1 SPECIFIES A SIMPSON
 METAM 24. THIS CONNECTOR WAS NOT LISTED IN THE 2008
 SIMPSON CATALOG OR WEBSITE. SUBMIT PRODUCT APPROVALS
 FOR THIS CONNECTOR.
  
 19) IN THE WIND INFORMATION ON SHEET A1 WALL ZONE 5 IS
 INCORRECTLY SPECIFIED AS AN INTERIOR ZONE. FIGURE
 R301.2(8)
  
 20) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS ARE EXPIRED. SUBMIT CURRENT ONES. DCA RULE
 9B-72.
  
 21) SPECIFY WHICH ONE OF THE BUR ROOFING SYSTEMS LISTED
 IN THE PRODUCT APPROVALS WILL BE USED. CIRCLE THE
 FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED.
 SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING.
  
 22) SPECIFY THE FASTENERS THAT WILL BE USED TO INSTALL
 THE STORM PANELS. CIRCLE THE APPROPRIATE ONE ON THE
 PRODUCT APPROVALS.
  