| 2008-04-10 06:56:22 | 2004 FBC W/2007 REVISIONS |
| | R-3ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | WILL BE REQUIRED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN THAT |
| | SPECIFIES THE DISTANCES FROM THE PROPOSED ADDITION TO |
| | THE PROPERTY LINES. |
| | |
| | 4) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC |
| | 13-600. |
| | |
| | 5) THE MINIMUM INSULATION FOR 2 X 6 FRAME WALLS IS |
| | R-19. THE MINIMUM INSULATION FOR RAISED WOOD FLOORS IS |
| | R-11. REVISE WALL SECTION ON A1. SEE FBC 13-602 AND |
| | 13-605. |
| | |
| | 6) SPECIFY THE TERMITE TREATMENT THAT WILL BE USED ON |
| | THE PLAN AS REQUIRED BY FBC R320.1. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R408.1 VENTILATION. THE |
| | UNDER-FLOOR SPACE BETWEEN THE BOTTOM OF THE FLOOR |
| | JOISTS AND THE EARTH UNDER ANY BUILDING (EXCEPT SPACE |
| | OCCUPIED BY A BASEMENT OR CELLAR) SHALL BE PROVIDED |
| | WITH VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR |
| | EXTERIOR WALLS. THE MINIMUM NET AREA OF VENTILATION |
| | OPENINGS SHALL NOT BE LESS THAN 1 SQUARE FOOT FOR EACH |
| | 150 SQUARE FEET (0.67 M 2 FOR EACH 100 M 2 ) OF UNDER |
| | -FLOOR SPACE AREA. ONE SUCH VENTILATING OPENING SHALL |
| | BE WITHIN 3 FEET (914 MM) OF EACH CORNER OF SAID |
| | BUILDING. |
| | |
| | 8) SHOW COMPLIANCE WITH R408.3 ACCESS. |
| | ACCESS SHALL BE PROVIDED TO ALL UNDER -FLOOR SPACES. |
| | ACCESS OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF |
| | 18 INCHES BY 24 INCHES (457 MM BY 610 MM). OPENINGS |
| | THROUGH A PERIMETER WALL SHALL BE 16 INCHES BY 24 |
| | INCHES (407 MM BY 610 MM). WHEN ANY PORTION OF THE |
| | THROUGH WALL ACCESS IS BELOW GRADE, AN AREAWAY OF NOT |
| | LESS THAN 16 INCHES BY 24 INCHES (407 MM BY 610 MM) |
| | SHALL BE PROVIDED. THE BOTTOM OF THE AREAWAY SHALL BE |
| | BELOW THE THRESHOLD OF THE ACCESS OPENING. THROUGH WALL |
| | ACCESS OPENINGS SHALL NOT BE LOCATED UNDER A DOOR TO |
| | THE RESIDENCE. SEE M1305.1.4 FOR ACCESS REQUIREMENTS |
| | WHERE MECHANICAL EQUIPMENT IS LOCATED UNDER FLOORS. |
| | |
| | 9) THE EXTERIOR WALL SECTION ON A1 DOES NOT APPEAR TO |
| | PROVIDE A SIX INCH CLEARANCE FOR TERMITE INSPECTION. |
| | SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR |
| | TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| | |
| | 10) PROVIDE A DETAIL INDICATING THE ATTACHMENT OF THE |
| | NEW FOUNDATION AND FRAME WALLS TO THE EXISTING |
| | STRUCTURE. |
| | |
| | 11) THE ATTIC VENTS SPECIFIED ON THE EXTERIOR WALL |
| | SECTION WILL HAVE TO BE CONTINUOUS IN ORDER TO PROVIDE |
| | VENTILATION TO THE SINGLE ASSEMBLY ROOF SYSTEM. SEE |
| | R806.1. |
| | |
| | 12) SPECIFY THE WINDOW TYPE AND SIZE FOR THE LAUNDRY |
| | ROOM WINDOW. FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL |
| | REINFORCING IN THE STEM WALL. |
| | |
| | 14) SPECIFY THE SIZE OF THE HORIZONTAL REINFORCING IN |
| | THE BOND BEAM FOR THE STEM WALL. |
| | |
| | 15) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE FRAME WALL TO THE FLOOR JOIST AS REQUIRED FOR A |
| | CONTINUOUS LOAD PATH. R301.1 |
| | |
| | 16) THE WALL SECTION ON A1 SPECIFIES 2 X 12 PT FLOOR |
| | JOISTS @ 16" OC WITH A 2 X 10 BAND. THE FLOOR FRAMING |
| | PLAN ON A1 SPECIFIES 2 X 10 JOISTS @ 16" OC. PLEASE |
| | CORRECT. |
| | |
| | 17) THE INFORMATION ON THE DIAPHRAGM SCHEDULE ON A1 |
| | CONFLICTS WITH THE NOTES ON THE EXTERIOR WALL SECTION |
| | FO THE ROOF AND WALL SHEATHING FASTENING. |
| | |
| | 18) THE EXTERIOR WALL SECTION ON A1 SPECIFIES A SIMPSON |
| | METAM 24. THIS CONNECTOR WAS NOT LISTED IN THE 2008 |
| | SIMPSON CATALOG OR WEBSITE. SUBMIT PRODUCT APPROVALS |
| | FOR THIS CONNECTOR. |
| | |
| | 19) IN THE WIND INFORMATION ON SHEET A1 WALL ZONE 5 IS |
| | INCORRECTLY SPECIFIED AS AN INTERIOR ZONE. FIGURE |
| | R301.2(8) |
| | |
| | 20) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG |
| | WINDOWS ARE EXPIRED. SUBMIT CURRENT ONES. DCA RULE |
| | 9B-72. |
| | |
| | 21) SPECIFY WHICH ONE OF THE BUR ROOFING SYSTEMS LISTED |
| | IN THE PRODUCT APPROVALS WILL BE USED. CIRCLE THE |
| | FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED. |
| | SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING. |
| | |
| | 22) SPECIFY THE FASTENERS THAT WILL BE USED TO INSTALL |
| | THE STORM PANELS. CIRCLE THE APPROPRIATE ONE ON THE |
| | PRODUCT APPROVALS. |
| | |