Date Text
2008-08-04 09:32:08 
 **DENIED4TH REVIEW**
  
 ** COMMENT FROM PREVIOUS REVIEW IS STILL IN NEED OF
 ATTENTION ALONG WITH SEVERAL NEW COMMENTS BASED ON
 CHANGE OF USE IN SOME ROOMS.
  
  
 1) NOTE: PLEASE COORDINATE ALL SHEETS IN SETS. PLEASE
 SEE NOTES FROM PREVIOUS REVIEW WHICH REQUEST TO REMOVE
 ALL SHEETS AND ONLY INSERT NEW SHEETS INTO THE
 COMPLETED SETS. THE NEW PLANS SUBMITTED HAVE SHEETS
 FROM PREVIOUS REVIEW DATED BACK TO PLANS SIGNED AND
 SEALED IN MARCH.
  
 2) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2,
 13-415.2.B.1.
 PLEASE PROVIDE THE CORRECT USE ON INPUT DATA REPORT AND
 SUMMARY SHEETS. IF MEDICAL THEN MEDICAL USE SHOULD BE
 STATED IN THOSE AREAS.
  
 3) NOTE: IT IS THE UNDERSTANDING OF THIS OFFICE THAT
 SOME MEDICAL PROCEDURES WILL BE IN SOME LOCATIONS IN
 THIS BUILD OUT. PLEASE SEE IN FACT THE LIGHTING PLANS
 HAVE NOW BEEN UPDATED TO INCLUDE A NOTE FOR WIRING OF
 LIGHTS AND ALSO A NEW UPS FOR BACK UP AS REQUIRED PER
 NEC 517.45. IN FACT THE PLANS ALSO NOTE TO SEE E-1 FOR
 DETAILS HOWEVER E-1 SHEETS ARE THE SAME SHEETS
 PREVIOUSLY SUBMITTED THROUGH OUT PROJECT WITH NO NEW
 DESIGNS.
 THE RISER AND BRANCH CIRCUITS ON PANELS DO NOT INDICATE
 ANY UPS SYSTEM FOR BACK UP POWER.
 THE PLANS DO NOT INCLUDE ANY INFORMATION FOR TIME OF
 BACK UP.
 THE PLANS DO NOT INDICATE ANY LOCATIONS FOR EQUIPMENT
 OR WIRING OF SYSTEMS.
 THE PLANS DO NOT INDICATE THE REDUNDANT GROUNDING AS
 REQUIRED PER 517.10
 PLEASE SEE 517 FOR ALL AREAS WHICH ARE SPECIFIC TO
 MEDICAL USE.
  
 4) NOTE: PLANS WILL BE ROUTED TO ALL OTHER TRADES FOR
 REVIEW OF ROOMS FOR MEDICAL PROCEDURES.
  
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  