| Date |
Text |
| 2008-07-09 13:16:49 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE NOTES FROM PREVIOUS REVIEW. |
| | THIS OCCUPANCY IS NOT A HOSPITAL WITH OPERATING ROOMS |
| | ETC. IF THIS IS GOING TO CONTAIN OPERATING ROOMS AND |
| | ANY USE WHICH FALLS UNDER THE DEFINITIONS OF A HOSPITAL |
| | THEN ALL PLANS FOR ALL TRADES INCLUDING BUILDING, |
| | MECHANICAL AND PLUMING NEED TO BE REVISED ACCORDINGLY |
| | TO MEET REQUIREMENTS OF A HOSPITAL. |
| | AS THIS IS NOT A HOSPITAL, MAY NOT USE ALLOWANCES FOR A |
| | HOSPITAL, OPERATING ROOMS ETC. PLEASE ADJUST. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND TABLE |
| | 13-415.2.B. |
| | PLEASE BE SURE ALL OTHER COMPONENTS ARE FILLED OUT IN |
| | THE INPUT DATA REPORT. |
| | WHERE IS PIPING? |
| | WHERE IS HOT WATER HEATING? |
| | ** THESE ARE SOME ITEMS WHICH ARE MOST CERTAINLY |
| | REQUIRED BY CODE AS WELL AS SHOWN ON PLANS. |
| | 13-411, 13-412 ETC |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |