Plan Review Notes
Plan Review Notes For Permit 08030667
Permit Number 08030667
Review Stop E
Sequence Number 3
Notes
Date Text
2008-07-09 13:16:49** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE NOTES FROM PREVIOUS REVIEW.
 THIS OCCUPANCY IS NOT A HOSPITAL WITH OPERATING ROOMS
 ETC. IF THIS IS GOING TO CONTAIN OPERATING ROOMS AND
 ANY USE WHICH FALLS UNDER THE DEFINITIONS OF A HOSPITAL
 THEN ALL PLANS FOR ALL TRADES INCLUDING BUILDING,
 MECHANICAL AND PLUMING NEED TO BE REVISED ACCORDINGLY
 TO MEET REQUIREMENTS OF A HOSPITAL.
 AS THIS IS NOT A HOSPITAL, MAY NOT USE ALLOWANCES FOR A
 HOSPITAL, OPERATING ROOMS ETC. PLEASE ADJUST.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND TABLE
 13-415.2.B.
 PLEASE BE SURE ALL OTHER COMPONENTS ARE FILLED OUT IN
 THE INPUT DATA REPORT.
 WHERE IS PIPING?
 WHERE IS HOT WATER HEATING?
 ** THESE ARE SOME ITEMS WHICH ARE MOST CERTAINLY
 REQUIRED BY CODE AS WELL AS SHOWN ON PLANS.
 13-411, 13-412 ETC
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved