| 2008-04-12 13:56:19 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE CITY WPB |
| | |
| | 1. SHT A-1 DETAIL #1 IN THE REMOVAL OF ANY PART OF A |
| | DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION |
| | 704.5. DEMO'D PIPING SHALL BE REMOVED BACK TO THE |
| | BRANCH LINE OR BLDG DRAIN. |
| | |
| | 2. SHT A-3 THE FLUSH CONTROLS OF THE W/C SHALL BE ON |
| | THE WIDE SIDE OF THE W/C. SECTION 11-4.16.5. (SHOWN ON |
| | THE WALL SIDE). |
| | |
| | 3. SHT P-1 WATER HEATER PIPING DIAGRAM. THE EXPANSION |
| | RELIEF VALVE SHALL DRAIN INTO THE HUB DRAIN WITH AN AIR |
| | GAP, OR THE WATER HEATER SHALL BE RAISED ABOVE THE PAN |
| | DRAIN OPENING. |
| | |
| | 4. SHT P-1 KEY NOTES #11 INDICATE THE TERMINATION POINT |
| | FOR THE CONDENSATE FROM THE AHU. CONDENSATE SHALL NOT |
| | DRAIN INTO THE SANITARY SYSTEM, BUT SHALL CONNECT TO A |
| | DEDICATED CONDENSATE RISER OR SHALL DRAIN SEPARATELY |
| | FROM THE BUILDING. ARTICLE III SECTION 90-125(B)(5). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |