Plan Review Notes
Plan Review Notes For Permit 08030667
Permit Number 08030667
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-12 13:56:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE CITY WPB
  
 1. SHT A-1 DETAIL #1 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5. DEMO'D PIPING SHALL BE REMOVED BACK TO THE
 BRANCH LINE OR BLDG DRAIN.
  
 2. SHT A-3 THE FLUSH CONTROLS OF THE W/C SHALL BE ON
 THE WIDE SIDE OF THE W/C. SECTION 11-4.16.5. (SHOWN ON
 THE WALL SIDE).
  
 3. SHT P-1 WATER HEATER PIPING DIAGRAM. THE EXPANSION
 RELIEF VALVE SHALL DRAIN INTO THE HUB DRAIN WITH AN AIR
 GAP, OR THE WATER HEATER SHALL BE RAISED ABOVE THE PAN
 DRAIN OPENING.
  
 4. SHT P-1 KEY NOTES #11 INDICATE THE TERMINATION POINT
 FOR THE CONDENSATE FROM THE AHU. CONDENSATE SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM, BUT SHALL CONNECT TO A
 DEDICATED CONDENSATE RISER OR SHALL DRAIN SEPARATELY
 FROM THE BUILDING. ARTICLE III SECTION 90-125(B)(5).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]