2008-04-28 10:57:21***DENIED***
  
 1) THE PLANS INDICATE AN OCCUPANT LOAD OF 52 UNDER
 PROJECT DATA. NFPA 101, 2003 SECTION 7.2.1.4.2 REQUIRES
 EGRESS DOORS TO SWING IN THE DIRECTION OF TRAVEL.
 PLEASE ADVISE IF EXCEPTION HAS BEEN MET.
  
 2) PLEASE SEE BUILDING COMMENT #2 REGARDING EXITING
 THROUGH A STORAGE AREA.
  
 3) PLANS INDICATE FIRE ALARM EQUIPMENT. PLEASE ADD TO
 ELECTRICAL LEGEND TO VERIFY SPECIFIC EQUIPMENT.
  
 4) PLANS DO NOT ILLUSTRATE FIRE SPRINKLER LAYOUT.
 SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 BOTH FIRE SPRINKLER AND FIRE ALARM REMODEL WHEN
 APPLICABLE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW