2008-03-31 17:07:51RESIDENTIAL RE-ROOF BUILDING REVIEW CHECKLIST. REVIEW
 UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH GENERAL LIMITATION
 #7OF NOA 03-0501.02AND NAIL ENHANCING SUBMITTED.
  
  
 2- SPECIFY SPECIFIC BASE SHEET FASTENING OPTION IF
 SELECTED ASSEMBLY HAS SEVERAL FASTENING OPTIONS.
  
 3- SPECIFY HOW COMPLYING WITH THE SECONDARY WATER
 BARRIER AS REQUIRED BY SEC. FS553.844(5)(A).
  
 4- NAIL ENHANCING FASTENING SHOWN ON SECOND PAGE OF
 HIGH VELOCITY PERMIT APPLICATIONSUBMITTED DOESN'T
 WORK FOR THE CALCULATED DESIGN PRESSURES.ALSO, NEED
 TO SPECIFY FASTENER SPACING THAT WORKS FOR FIELD AREA.
 12"O.C. @ LAP AND 2 ROWS @ 12"O.C. DON'T RESIST THE
 -52.5PSF.TO AVOID CONFUSIONS, PLEASE DON'T USE
 ANOTHER MUNICIPALITY PERMIT APPLICATIONS FORMS.
 PROVIDE REQUIRED INFORMATION ON SEPARATE SHEETS WITH
 CONTRACTOR'S LETTER HEAD TO SIMPLIFY PROCESS. SEE
 ATTACHED CITY POLICY FOR ROOFING PERMITS.PROVIDE
 ACTUAL RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 5- THIS JURISDICTION HAS NOT ADOPTED THE RAS 150.
  