| 2008-04-03 13:51:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) THE ENERGY CALCULATIONS FOR THIS PROJECT CAN NOT USE |
| | FORM 400A, SEE 2004 FBC 13-101.1.3. |
| | |
| | 2) WHEN DOING THE ENERGY CALCULATIONS DO NOT USE THE |
| | COMPUTER PROGRAM VERSION 2.11 YOU WILL NEED TO USE 2.5, |
| | SEE 2004 FBC 13-400.3.A, 13-400.3.B, 13-400.3.C, AND |
| | TABLE 13-400.3.ABC.3. |
| | |
| | 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 |
| | FBC 13-407.1.ABC.1. |
| | |
| | 4) IF THE A/C CONDENSER STANDS ON THE ROOF ARE EXISTING |
| | PLEASE STATE SO ON THE MECHANICAL PLAN. IF NEW PLEASE |
| | SUBMIT PRODUCT APPROVAL OR AN NOA FOR PER-ENGINEERED |
| | CONDENSER STANDS, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| | 9B-72.005, AND FAC 9B-72.010(31)(G). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |
| | *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND |
| | SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. |
| | AMEND. 106.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |