Plan Review Notes
Plan Review Notes For Permit 08030648
Permit Number 08030648
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-02 15:20:37** DENIED**
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON ELECTRICAL AS WELL AS ARCHITECTURAL SHEETS. SOME OF
 THESE ARE ALREADY LISTED HOWEVER SOME CHANGES ARE
 NEEDED.
 2004 FBC W/2007 REVISIONS.
 2002 NFPA-72 (IF FIRE ALARM SYSTEM IS PRESENT)
 PLANS DO CALL FOR FA SYSTEM.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, 13-400.3.A,
 13-400.3.B, 13-400.3.C, 13-101.1.2 AND .1.3.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS.13-415.2.ABC.1.1, .1.2 AND .1.3.
 FIRST ITEM IS THE METHOD SUBMITTED FOR ENERGY
 CALCULATIONS IS THAT OF METHOD *A* WHICH IS FOR WHOLE
 BUILDING COMPLIANCE. THIS IS NOT A WHOLE BUILDING; THIS
 METHOD *A* IS NOT AN OPTION.
 PLEASE ALSO SEE THAT IN ANY CASE THE VERSION MUST BE
 THE ADOPTED VERSION PER THE FBC. THE VERSION 2.11
 SUBMITTED WAS UNDER THE OLDER 2004 CODE. THE VERSION
 CHANGED ON DEC 8TH, 2006 WHICH IS ALMOST ONE AND HALF
 YEARS AGO.
 PLEASE SEE THE PLANS DO NOT CORRELATE WITH THE INPUT
 DATA REPORT.
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING WHICH STATES ONLY ONE
 FIXTURE TYPE WHICH IS 26W EACH HOWEVER THE PLANS
 CONTAINS NUMEROUS OTHER FIXTURES WHICH ARE NOT PART OF
 THE IDR. HOW IS THIS POSSIBLE? PLEASE BE SURE ALL ON
 PLANS COORDINATES WITH THE CALCULATIONS.
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING CALCULATIONS ON PLANS WHICH
 CONTAIN MANY MORE FIXTURES. EXTERIOR IS BLANK ON THE
 IDR?
 PLEASE SEE THE PRINTING OF THE OWNER AGENT AS A COMPANY
 IS NOT ACCEPTABLE. THIS REQUIRES A SIGNATURE FROM THE
 OWNER AGENT.
  
 2) NOTE: PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 3) NOTE: PLEASE GIVE THE MAXIMUM TIMES ON THE OCCUPANCY
 DEVICES. 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE COMPLETE ALL LOCATIONS FOR DEVICES PER
 THE PROPOSED FA SYSTEM PER FBC ADA REQUIREMENTS
 11-4.28.1,.2 AND .3(4). MINIMUM LOCATIONS AND MINIMUM
 LEVELS FOR DEVICES ARE NEEDED.
  
 5) NOTE: PLEASE SEE NOTE #1 ABOVE WITH RESPECT TO
 LIGHTING ON PLANS AND ALSO COMPLETE INFORMATION FOR
 ITEMS WHICH ARE SHOWN AS J-BOXES IN CALCULATIONS FOR
 PERFORMANCE LEVELS. 13-415.2.
  
 6) NOTE: PLANS/PANEL SCHEDULE INDICATES A SMOKE ALARM
 CIRCUIT. WHAT IS THIS? SEE NFPA-72 DEFINITIONS AND
 NOTES ABOVE WITH RESPECT TO ANY MINIMUM DESIGNS
 REQUIRED.
 PLEASE ALSO COORDINATE THE LOAD ON PANEL WITH THAT OF
 THE LOAD SHOWN ON LOAD CALCULATIONS FOR THIS SAME
 CIRCUIT.
  
 7) NOTE: PLEASE VERIFY ROOF-TOP GFI PER 210.8B, 210.63.
  
 PLANS INDICATE A GFI LOCATED ABOVE THE CEILING OF
 BATHROOM FOR THE AHU, HOWEVER THIS IS NOTED ON PANEL
 SCHEDULE AS ROOF-TOP?
  
 8) NOTE: PLEASE ALSO SUBMIT DETAIL/INFORMATION FOR THE
 REQUIRED DISCONNECT FOR THE CU. 440.11.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]