| 2008-04-07 12:46:06 | BUILDING PLAN REVIEW |
| | PERMIT: 08030648 |
| | ADD: 1335 OKEECHOBEE BLVD |
| | CONT: E.W. KELSON BUILDERS INC. |
| | TEL: (561)793-5876 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 3)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO |
| | INCLUDE STRUCTURAL, ELECTRIC, PLUMING, MECHANICAL, |
| | INTERIOR FINISH, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS AND OVERHEAD AND PROFIT. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST |
| | ANALYSIS SERVICES PER FBC 108.3* |
| | |
| | 5)PROVIDE A FIRE SPRINKLER HEAD PLAN SHOWING THE |
| | LOCATION OF THE SPRINKLER IN RELATION TO THE WALLS AND |
| | OFFICES. FBC 106.3.1.1(5) |
| | |
| | 6)11-4.13.6 |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIGURE |
| | 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE LEVEL AND CLEAR. THE MINIMUM |
| | CLEARANCE AT THE PULL SIDE SHALL BE 18 INCHES. |
| | 7)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. |
| | |
| | 8)PROVIDE A FINISH SCHEDULE FOR ALL THE ROOMS AND |
| | INDICATE THE WALLS AND FLOOR FINISHES FOR EACH ROOM. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |