| 2008-04-03 16:27:43 | | | | | | | DENIED | | | | | | 1) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THATIS RELEVANT PER 9B-72. | | | THESE SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER | | | PAGES, AND THE PRODUCT NOA THAT LISTS THE SYSTEM | | | COMPONENTS/ FASTENER LIST PAGES. ALL CAN BE FOUND ON | | | WWW.FLORIDABUILDING.ORG ******ONLY ONE COPY OF | | | PRODUCT APPROVAL WAS SUBMITTED*********** | | | | | | 2) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST. OUR | | | VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND | | | MEANS COST ANALYSIS SERVICES PER | | | 108.3 FBC********OUR COST SHEETS VALUE BAHAMA | | | SHUTTERS AT $30 + PER SQUARE FOOT********* | | | | | | 3)SHUTTER PERMIT APPLICATIONS REQUIRE 2 COPIES OF A | | | KEY PLAN (WITH EGRESS AND OPENING SIZES SHOWN), SHUTTER | | | SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS | | | SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE | | | AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT | | | INFORMATION SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, | | | MOUNTING CONNECTION METHOD, ANCHOR TYPE, SHUTTER SPAN | | | (VERTICAL OR HORIZONTAL), ETC.) ******* PLEASE SEE THE | | | ATTACHED MEMO AND SCHEDULE.******* | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|