| Plan Review Notes For Permit 08030602 |
| Permit Number |
08030602 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-28 16:40:42 | REROOF FORR2 BUILDING.BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | 2- THERE IS A NOTE ON PAGE 1 OF NOA 03-0501.02 THAT | | | APPROVED ASSEMBLY TO BE USED IS ON PAGE 9 AND 10, WHICH | | | IS ANINSULATEDASSEMBLY.BUT,ENGINEER | | | CALCULATIONS FOR NAIL ENHANCING SPECIFIES SHEETS 26 AND | | | 27 WHICH IS A NON-INSULATED ASSEMBLY.CONTRACTOR AND | | | ENGINEERTO COORDINATE AND DECIDE WHICH ASSEMBLY IS | | | GOING TO BE INSTALLED. THEN PROVIDE CORRESPONDING | | | INFORMATION THAT MATCHES. | | | | | | 3- RAS 117 CALCULATIONS FOR NAIL ENHANCING DONE BY R. | | | N. SAILAPPAN, PE.NEED TO BE REVISED.ACCORDING TO | | | CALCULATIONS SHOWN ABOVE THE RECOMMENDED BASE SHEET | | | ATTACHMENT PATTERNTHE ANCHOR SPACING FOR 3 ROWS IN | | | THE FIELD SHEET OF PERIMETER AREA IS 6"O.C.NOT 9". | | | AND, THE ANCHOR SPACING FOR 3 ROWS IN THE FIELD OF | | | CORNER AREAS IS 4"O.C.NOT 6". | | | ***NOTE: ENGINEER TO COORDINATE WITH CONTRACTOR | | | SPECIFIC APPROVED ASSEMBLY TO BE INSTALLED.SEE ITEM | | | ONE ABOVE. | | | | | | 4- OWES $37.65 FOR UPDATED VALUATION AS REQUIRED BY | | | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|