| 2008-05-01 16:05:56 | ** DENIED2ND REVIEW ** |
| | |
| | ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF |
| | ADDRESSING ALONG WITH NEW COMMENTS DUE TO DOCUMENTS NOW |
| | SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW AS THE |
| | ELECTRICAL RISER DOES NOT COORDINATE WITH THE RISER |
| | PREVIOUSLY SUBMITTED OR THE NEW RISER. |
| | THE RISER SHOWS ONLY THE METER OUTSIDE. |
| | FBC 106.1.2, 106.3.5.4 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | NEC 225.31-225.39, 230.70, 230.72 ETC |
| | |
| | 2) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS. THE |
| | NEW SHEETS NOW SUBMITTED ARE LOOSE FROM TWO PREVIOUS |
| | SETS. |
| | PLEASE ALSO SEE THE NEW REVISED RISER DOES NOT CONTAIN |
| | ANY PRINTED NAME, DATE AND SIGNATURE BY THE RESPONSIBLE |
| | DESIGNER PER FS471.003, EXCEPTIONS, 489. |
| | PLEASE COMPLETE. |
| | FBC 106.3.1 |
| | |
| | 3) NOTE: PLEASE SEE THAT HEAT LOAD MAY NOT BE DE-RATED |
| | AT 65%. |
| | LOAD FOR HEAT STRIP MAY ONLY BE DE-RATED IF LOAD |
| | SHEDDING DEVICES/SYSTEM WILL BE USED. |
| | PLEASE ADJUST. |
| | 220, 702.5 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |