| Notes |
| Date |
Text |
| 2008-03-25 14:45:19 | 2004 FBC W/2007 REVISIONS | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE C, HOWEVER THE | | | DESIGN PRESSURE CALCULATION IS FOR EXPOSURE B. REVISE | | | THE OPENING WIND LOAD PRESSURES. SEE FBC R301.2.1.4 AND | | | TABLE 301.2(2). | | | | | | 2) NOTE: THE LOCATION OF THE OPENING IS IN THE INTERIOR | | | ZONE NOT THE END ZONE AS SPECIFIED ON THE CALCULATION. | | | | | | | | | 3) SPECIFY THE HEADER TYPE AND LENGTH ON SCHEDULE 'J' | | | PAGES 13 AND 14 OF DRAWINGS. FBC 106.1.1* CITY | | | AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|