Plan Review Notes
Plan Review Notes For Permit 08030519
Permit Number 08030519
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-26 15:31:47 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1) PROVIDE A RISER DIAGRAM SHOWING LOCATIONS OF ALL
 EQUIPMENT ELECTRICALLY. 215.5.
  
 2) PROVIDE A SITE PLAN INDICATING THE PHYSICAL LOCATION
 OF THE EQUIPMENT WITH REGARD TO THE SERVICE AND
 SEPARATE STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE
 SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER
 SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING
 MEANS. ALSO 110.9 FOR AIC RATING.
  
 3) IDENTIFY LOADS TO BE SERVED, PANEL SCHEDULE FOR
 GENERATOR PANEL. LOADS MUST NOT EXCEED GENERATOR
 OUTPUT.702.5
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  