| 2008-08-28 09:48:26 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A1 SCOPE OF WORK: THE SCOPE OF WORK IS NOT |
| | CLEAR DUE TO A SUBMITTED SANITARY ISOMETRIC RISER |
| | DIAGRAM BEING INDICATED ON SHEET A2. PLEASE CLARIFY IF |
| | IT IS THE INTENT TO REPLACE THE SANITARY SYSTEM WITH |
| | NEW PIPE IN THE SCOPE OF WORK. PLEASE KNOW THAT A |
| | PLUMBING PERMIT WILL BE REQUIRED IF THAT IS THE INTENT. |
| | PER (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. SHEET A2 SANITARY PLUMBING RISER: PLEASE CORRECT |
| | THE FOLLOWING PER THE FBC-2004 PLUMBING SECTIONS. |
| | |
| | A} THE RISER DIAGRAM DOES NOT RELECT THE FLOOR PLAN. |
| | THE KITCHEN SINK BEING INDICATED ON SHEET A1 HAS TWO |
| | BOWLS. CLEARLY INDICATE THIS ON THE RESUBMITTAL. PER |
| | SECTION 701.1 SCOPE. |
| | |
| | B} SIZE ALL WASTE PIPING AND WATER-SEAL TRAPS. PER |
| | SECTION 701.1 SCOPE. |
| | |
| | C} HORIZONTAL WASTE PIPING AND STACK FOR THE WASHING |
| | MACHINE SHALL BE 3 INCH AND THE WASHING MACHINE |
| | WATER-SEAL TRAP SHALL BE 2 INCH. PER SECTION 406.3 |
| | WASTE CONNECTIONS. |
| | |
| | D} A 3 INCH CLEANOUT FOR THE WASHING MACHINE STACK IS |
| | REQUIRED AND IT SHALL BE LOCATED AT FOUR FEET ABOVE |
| | FINNISH FLOOR (4" A.F.F.) PER SECTION 708.9 ACCESS. |
| | |
| | E} PER THE LOCATION OF THE WASTE STACK FOR THE KITCHEN |
| | SINK A 2 INCH WASTE ARM IS REQUIRED FOR THE KITCHEN |
| | SINK. PER TABLE 906.1 MAXIMUM DISTANCE OF FIXTURE TRAP |
| | FROM VENT. |
| | NOTE: WITH HAVING TO INSTALL A 2 INCH WASTE ARM FOR |
| | THE KITCHEN SINK PLEASE KNOW THAT THE STRUCTURAL |
| | INTEGRITY OF THE EXTERIOR WALL IS AFFECTED AND THE WALL |
| | WILL NEED TO BE INSTALLED PER FBC-2004 RESIDENTIAL |
| | SECTION R602.2.7 DRILLING AND NOTCHING-STUDS. |
| | |
| | F} THE LAVATORY WATER-SEAL TRAP CAN BE EITHER 1-1/4 |
| | INCH OR 1-1/2 INCH. PLEASE KNOW THAT IF ITS SIZED 1-1/4 |
| | INCH A CLEANOUT SHALL BE REQUIRED AT THE BASE OF ITS |
| | WASTE STACK. PER SECTION 708.7 MINIMUM SIZE, EXCEPTIONS |
| | (1), AND SECTION 708.3.5 BASE OF STACK. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |