| 2008-06-17 16:37:50 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | NOTE: THERE WERE NO COMMENT RESPONSES FROM THE |
| | DESIGNER. |
| | |
| | 1. PROVIDE SANITARY AND WATER ISOMETRIC RISER DIAGRAMS |
| | OF THE PROPOSED NEW MASTER BATHROOM PLUMBING LAYOUT AND |
| | NEW BAR SINK. PER (W.P.B. AS AMENDED) SECTION |
| | 106.3.5.1.3 PLUMBING (3)(4)(10)(13). |
| | |
| | **NO COMMENT RESPONSE AND COMMENT WAS NOT ADDRESSED. |
| | AN ISOMETRIC SANITARY AND WATER RISER DIAGRAMS ARE |
| | STILL REQUIRED FOR THE PROPOSED NEW MASTER BATHROOM |
| | PLUMBING LAYOUT. THE RESUBMITTED PLANS DO NOT INDICATE |
| | A SINK IN THE NEW BAR AS IT WAS SHOWN IN THE LAST SET |
| | OF PLANS. PLEASE CLARIFY IF THE BAR SINK IS BEING |
| | DELETED. IF IT IS NOT BEING DELETED IT ALSO NEEDS TO BE |
| | ON THE REQUIRED SANITARY AND WATER RISER DIAGRAMS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |