| 2008-05-28 14:08:16 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. |
| | |
| | 2) THIS UNIT IS LOCATED IN A HIGH RISE BUILDING. THE |
| | BUILDING IS REQUIRED TO BE TYPE 1A CONSTRUCTION. THE |
| | FRAMING IN THE NON-BEARING PARTITION WALLS IS REQUIRED |
| | TO BE FIRE-RETARDANT-TREATED WOOD OR NON-COMBUSTIBLE |
| | MATERIAL. SEE FBC 603.1. |
| | |
| | 3) PROVIDE DETAILS OF THE RAISED PLATFORMS. SPECIFY |
| | SIZE, HEIGHT AND MATERIALS THAT WILL BE USED TO |
| | CONSTRUCT. FBC 106.1.2* CITY AMENDMENTS |
| | |
| | 4) SHOW COMPLIANCE WITH 410.4 PLATFORM CONSTRUCTION. |
| | PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS |
| | AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING IN WHICH THE PERMANENT PLATFORMS IS LOCATED. |
| | PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV |
| | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN |
| | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN |
| | 3,000 SQUARE FEET (279 M 2 ) IN AREA. WHERE THE SPACE |
| | BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR |
| | ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR |
| | PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE |
| | SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR |
| | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE |
| | PERMANENT PLATFORM NEED NOT BE PROTECTED. |
| | |
| | 5) PROVIDE FLOOR PLANS OF THE PROPOSED REMODEL WITH |
| | DIMENSIONS, DOOR SIZES, ETC. SHOW LOCATIONS OF |
| | PLATFORMS. SEE FBC 106.1.1* CITY AMENDMENTS. |
| | |