Plan Review Notes
Plan Review Notes For Permit 08030509
Permit Number 08030509
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-24 10:02:592004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE PLANS SHOW THE RELOCATION AND ADDITION OF
 PLUMBING FIXTURES THAT WILL REQUIRE PENETRATIONS
 THROUGH THE FIRE RATED FLOOR. THE PLANS ARE REQUIRED TO
 BE SIGNED AND SEALED BY A FLORIDA LICENSED ARCHITECT OR
 ENGINEER. FS 471 AND 481.
  
 3) SHOW COMPLIANCE WITH 2004 FBC MECHANICAL SECTION
 402.3.1 FOR MECHANICAL VENTILATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]