| Notes |
| Date |
Text |
| 2008-03-24 10:02:59 | 2004 FBC W/2007 REVISIONS | | | LEVEL 2 ALTERATION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) THE PLANS SHOW THE RELOCATION AND ADDITION OF | | | PLUMBING FIXTURES THAT WILL REQUIRE PENETRATIONS | | | THROUGH THE FIRE RATED FLOOR. THE PLANS ARE REQUIRED TO | | | BE SIGNED AND SEALED BY A FLORIDA LICENSED ARCHITECT OR | | | ENGINEER. FS 471 AND 481. | | | | | | 3) SHOW COMPLIANCE WITH 2004 FBC MECHANICAL SECTION | | | 402.3.1 FOR MECHANICAL VENTILATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|