| Date |
Text |
| 2008-10-01 10:32:00 | ** DENIED REVIEW ** |
| | |
| | ** CONTACT TO THE ARCHITECT WAS ATTEMPTED BY THIS |
| | OFFICE TO THE NUMBER LISTED ON TITLE BLOCKS HOWEVER THE |
| | PHONE NUMBER WAS * NO LONGER IN SERVICE*. |
| | |
| | 1) NOTE: PLEASE SEE TIMER TYPE DEVICES MAY NOT BE USED |
| | PER FBC 11-4.27.4 FOR ANY AREAS WHICH ARE ADA |
| | ACCESSIBLE. |
| | |
| | 2) NOTE: PLEASE SEE THE NEW CONTROLS SHOWN FOR EGRESS |
| | STAIRS NEED TO MEET FB C1006.1.2, NFPA-101 7.8.1.2.2. |
| | ALL OCCUPANCY DEVICES BEING USED FOR EGRESS SHALL BE |
| | *FAIL SAFE ON* AND SHALL BE ON FOR A MINIMUM OF 15MINS. |
| | PLEASE ADJUST PLANS. |
| | |
| | 3) NOTE: PLEASE SEE THE FIXTURE LEGEND ON PLANS. AS THE |
| | FIXTURE LEGEND IS NOT COMPLETE WITH ALL WATTAGES MANY |
| | OF THESE CAN NOT BE CONFIRMED WITH THE SUBMITTED |
| | REVISED ENERGY CALCULATIONS. |
| | SOME EXAMPLES OF THIS WOULD BE C, D, DE, F, I ETC. |
| | THERE ARE OTHERS WHICH DO NOT INDICATE WATTAGES. |
| | 13-415.2,13-415.2.ABC.1.1, .1.2, .1.3. |
| | |
| | 4) NOTE: FOR INFORMATIONAL PURPOSE, THE RECORD NOTICE |
| | OF COMMENCEMENT IN THE PACKAGE IS EXPIRED PER FS |
| | 713.13(2). THE RECORDING DATE WAS NOV OF 2007. WHEN |
| | WORK DOES NOT COMMENCE WITHIN 90DAYS OF RECORDING IT |
| | BECOMES VOID. THIS WILL ONLY NEED TO BE RE-RECORDED. |
| | THIS IS NOT AN ELECTRICAL PLAN REVIEW COMMENT AND ONLY |
| | MADE TO BENEFIT THE CONTRACTOR/OWNER. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |