Plan Review Notes
Plan Review Notes For Permit 08030500
Permit Number 08030500
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-07 17:03:01** DENIED2ND REVIEW **
  
 ** PLEASE KNOW THERE ARE SEVERAL ITEMS STILL FROM
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 MANY OF THESE ARE THE EXACT SAME COMMENTS.
  
 ** IT IS IMPORTANT TO SEE NOTES FROM PREVIOUS REVIEW.
  
 ** AS STATED ON PREVIOUS REVIEW DUE TO THE FACT SOME
 INFORMATION IS STILL NOT YET SUBMITTED THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
 ** THERE ARE ALSO SOME NEW COMMENTS BASED ON DOCUMENTS
 AND INFORMATION NOW BEING SUBMITTED OR SHOWN WHICH WAS
 NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND
 SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 ** THIS IS THE SAME COMMENT AS ON PREVIOUS REVIEW.
 RESPONSE MENTIONS TO SEE LS PLANS YET THE ELECTRICAL
 PLANS ARE REQUIRED TO CONTAIN RELEVANT CODE
 REFERENCES.
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS.
 THERE ARE MANY NEW DEVICES SHOWN ON PLANS YET MINIMUM
 REQUIRED FOR LIGHTING CONTROLS HAS NOT BEEN MET.
 THERE ARE NOW NEW TS (TIMED SWITCH) DEVICES IN MANY
 LOCATIONS HOWEVER AS THE DEVICE IS NOT SPECIFIC
 DETERMINATION FOR COMPLIANCE CAN NOT BE MADE.
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL SEVERAL STANDARD SINGLE POLE
 SWITCHES STILL BEING SHOWN FOR ACCENT LIGHTING.
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN FOR
 OTHER AREAS FOR GENERAL LIGHTING. (HALL OUTSIDE TOILET
 110)
  
 ** FOR EXAMPLE:
 PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH THE
 LIGHTING CONTROLS ARE NOT LOCATED IN THE SEPARATE SPACE
 AS REQUIRED. THIS CAN BE CLEARLY SEEN ON THE UPPER
 LEVEL WHERE THE CONTROLS ARE LOCATED IN THE HALLWAY FOR
 CONTROLLING LIGHTING WHICH IS ACTUALLY LOCATED IN
 OFFICES/OR ROOMS.
  
 ** FOR EXAMPLE:
 CONTROL FOR OUTSIDE LIGHTING DOES NOT MEET
 13-415.1.ABC.1.4.
  
 ** FOR EXAMPLE:
 PLEASE CLARIFY THE LIGHTING CONTROLS NOTES WHICH
 MENTION *STORE*. THIS IS SUBMITTED AS A BUSINESS
 OCCUPANCY AND NOT A RETAIL STORE.
  
 ** THESE ARE ONLY A FEW EXAMPLES AND ARE NOT AN
 EXHAUSTED LIST OF MANY ITEMS WHICH NEED TO BE
 ADDRESSED.
 PLEASE LOOK AT OTHER COMMENTS BELOW AS THESE WILL
 AFFECT LIGHTING CONTROLS.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS MEETING THE MINIMUM REQUIRED BY THE LIFE
 SAFETY CODE.THIS WAS REQUESTED ON PREVIOUS REVIEW AND
 THERE ARE SOME SEPARATE SHEETS SHOWING SOME LEVELS
 HOWEVER THE LEVELS SHOWN DO NOT MEET THE MINIMUM
 REQUIRED.
 PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ARE
 REQUIRED TO BE 10FT CANDLES UNDER NORMAL. THE SEPARATE
 SHEETS SHOW 7.
 PLEASE SEE THE EMERGENCY LEVELS ARE PERMITTED TO GO
 DOWN TO 1FT CANDLE.
 7.9.2.1, 7.9.2.2
 THE LEVELS SHALL BE SHOWN AND PART OF THE RECORD SETS
 OF PLANS.
  
 4) NOTE: PLEASE SEE NFPA-101 2003 AND FBC 1006.1.2 FOR
 CONTROLS IN EGRESS AREAS. PLANS SHOW A STANDARD SINGLE
 POLE SWITCH AT THE BOTTOM OF STAIRS AND NO CONTROLS ON
 STAIRS OR AT THE TOP OF THE STAIRS.
 PLEASE SEE COMMENT #2 ABOVE WITH RESPECT TO LIGHTING IN
 BUILDINGS REQUIRED TO BE TURNED OFF.
 PLEASE ADDRESS.
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT
 SUBMITTING LIGHTING PERFORMANCE CALCULATIONS AND MAKING
 SURE ALL LIGHTING ON PLANS COORDINATES WITH THE INPUT
 DATA REPORT WHICH IS PART OF THE ENERGY CALCULATIONS.
 PLEASE SEE NOW A METHOD *A* IS BEING SUBMITTED WHICH
 CAN NOT BE USED AT THIS TIME. METHOD *A* IS FOR A WHOLE
 BUILDING WITH ALL KNOWN COMPONENTS. AS THIS BUILDING
 CONTAINS AREAS WHICH ARE SHOWN FOR *FUTURE BUILD OUT*
 THE *A* MAY NOT BE USED. PLEASE SEE 13-400.3.B,
 13-400.3.C, 13-101.1.6.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 ** THE SUBMITTED CALCULATIONS DO NOT COORDINATE WITH
 PLANS.
 SOME EXAMPLES OF THIS WILL BE NOTED BELOW HOWEVER THESE
 ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR.
  
 ** FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO EXTERIOR LIGHTING.
 HOW IS THIS POSSIBLE WHEN THE PLANS MOST CERTAINLY
 CONTAIN SEVERAL EXTERIOR LIGHTING FIXTURES?
  
 ** FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS ONE DOORS. HOW IS THIS
 POSSIBLE WHEN THE PLANS CERTAINLY CONTAIN DOORS FROM
 CONDITIONED SPACE TO UNCONDITIONED SPACE WHICH AS SHOWN
 EXCEED ONE?
  
 ** FOR EXAMPLE:
 PLEASE KNOW IF A METHOD *A* COULD BE USED ALL LIGHTING
 INCLUDING GARAGE AREA WOULD BE REQUIRED TO BE SHOWN IN
 THE IDR>
  
 ** FOR EXAMPLE:
 PLEASE VERIFY SOME LIGHTING CONTROLS NOTED * WITH
 DAYLIGHT ON/OFF*. WHERE ARE THESE ON PLANS?
  
 ** FOR EXAMPLE:
 NOT ALL FIXTURES ON PLANS ARE COMPLETED, SOME SHOWN AS
 *J* BOX ONLY.
  
 ** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT AND
 ARE NOT ALL ITEMS.
  
 6) NOTE: PLANS INDICATE SOME SORT OF TIMER SWITCH
 DEVICES YET AS THIS DEVICE IS NOT SPECIFIC AS NOTED
 ABOVE PLEASE SEE FBC 11-4.27 AND MORE SPECIFICALLY
 11-4.27.4 FOR TIME TYPE DEVICES.
  
 7) NOTE: PLEASE SHOW THE LOCATION OF THE PROPOSED
 SERVICE. 110.26, 240.4, 230.70, 230.71, 230.72 ETC
 FBC106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY.
  
 8) NOTE: PLEASE SEE 645.10. THERE IS A SHUNT TRIP
 PUSHBUTTON ON POWER PLANS NOTED OUTSIDE *IT* ROOM YET
 THIS DOES NOT PROVIDE THE DISCONNECTING MEANS AS
 REQUIRED IN SECTION ABOVE. AS THERE ARE CIRCUITS FROM
 TWO SEPARATE SOURCES INCLUDING PANELS *A* AND *B* BOTH
 WOULD REQUIRE BREAKERS IN EACH CIRCUIT OR PANEL. AS THE
 PANELS DO NOT INDICATE ANY DEVICES FOR REQUIRED
 DISCONNECT THE SCENARIO AS SHOWN DOES NOT MEET THE
 CODE.
 WHERE IS THE REQUIRED DISCONNECT FOR A/C EQUIPMENT?
 PLEASE BE SURE TO LOOK AT THE SECTION OF THE CODE NOTED
 AND PROVIDE A DIAGRAM OR COMPLETE PLANS SHOWING
 COMPLIANCE.
  
 9) NOTE: PLEASE COORDINATE ELECTRICAL PLANS WITH
 MECHANICAL PLANS FOR CONTROLS OF BATHROOM EXHAUST
 FANS.
 MECHANICAL CODE REQUIRES CONTROLS OTHER THAN THE SINGLE
 POLE SWITCH AS SHOWN ON ELECTRICAL PLANS. THIS IS A
 MECHANICAL CODE REQUIREMENT.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION AND CLARITY REQUIRES PLANS TO MATCH.
 FBC/MECHANICAL CODE 402.3.1
  
 10) NOTE:PLEASE VERIFY NEW OR EXISTING ROOF-TOP GFI
 FOR NEW IT ROOM UNIT .210.63, 210.8B
  
 11) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE ACCESS
 CONTROL SYSTEM OR WILL THIS BE UNDER SEPARATE PLANS AND
 PERMIT.
 PLEASE SEE NFPA-101 7.2.1.5, 7.2.1.6.2
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW SOME ELECTRICAL PLANS AS WELL AS
 CALCULATIONS WERE RETAINED BY THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]