| 2008-07-07 17:03:01 | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE KNOW THERE ARE SEVERAL ITEMS STILL FROM |
| | PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | MANY OF THESE ARE THE EXACT SAME COMMENTS. |
| | |
| | ** IT IS IMPORTANT TO SEE NOTES FROM PREVIOUS REVIEW. |
| | |
| | ** AS STATED ON PREVIOUS REVIEW DUE TO THE FACT SOME |
| | INFORMATION IS STILL NOT YET SUBMITTED THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN |
| | NOT BE MADE AT THIS TIME. |
| | |
| | ** THERE ARE ALSO SOME NEW COMMENTS BASED ON DOCUMENTS |
| | AND INFORMATION NOW BEING SUBMITTED OR SHOWN WHICH WAS |
| | NOT ON PREVIOUS PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| | REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND |
| | SCOPE OF WORK. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | ** THIS IS THE SAME COMMENT AS ON PREVIOUS REVIEW. |
| | RESPONSE MENTIONS TO SEE LS PLANS YET THE ELECTRICAL |
| | PLANS ARE REQUIRED TO CONTAIN RELEVANT CODE |
| | REFERENCES. |
| | |
| | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND |
| | .1.4 FOR MISSING LIGHTING CONTROLS. |
| | THERE ARE MANY NEW DEVICES SHOWN ON PLANS YET MINIMUM |
| | REQUIRED FOR LIGHTING CONTROLS HAS NOT BEEN MET. |
| | THERE ARE NOW NEW TS (TIMED SWITCH) DEVICES IN MANY |
| | LOCATIONS HOWEVER AS THE DEVICE IS NOT SPECIFIC |
| | DETERMINATION FOR COMPLIANCE CAN NOT BE MADE. |
| | ** FOR EXAMPLE: |
| | PLEASE SEE THERE ARE STILL SEVERAL STANDARD SINGLE POLE |
| | SWITCHES STILL BEING SHOWN FOR ACCENT LIGHTING. |
| | ** FOR EXAMPLE: |
| | PLEASE SEE THERE ARE STILL STANDARD DEVICES SHOWN FOR |
| | OTHER AREAS FOR GENERAL LIGHTING. (HALL OUTSIDE TOILET |
| | 110) |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE SEE THERE ARE SEVERAL AREAS IN WHICH THE |
| | LIGHTING CONTROLS ARE NOT LOCATED IN THE SEPARATE SPACE |
| | AS REQUIRED. THIS CAN BE CLEARLY SEEN ON THE UPPER |
| | LEVEL WHERE THE CONTROLS ARE LOCATED IN THE HALLWAY FOR |
| | CONTROLLING LIGHTING WHICH IS ACTUALLY LOCATED IN |
| | OFFICES/OR ROOMS. |
| | |
| | ** FOR EXAMPLE: |
| | CONTROL FOR OUTSIDE LIGHTING DOES NOT MEET |
| | 13-415.1.ABC.1.4. |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE CLARIFY THE LIGHTING CONTROLS NOTES WHICH |
| | MENTION *STORE*. THIS IS SUBMITTED AS A BUSINESS |
| | OCCUPANCY AND NOT A RETAIL STORE. |
| | |
| | ** THESE ARE ONLY A FEW EXAMPLES AND ARE NOT AN |
| | EXHAUSTED LIST OF MANY ITEMS WHICH NEED TO BE |
| | ADDRESSED. |
| | PLEASE LOOK AT OTHER COMMENTS BELOW AS THESE WILL |
| | AFFECT LIGHTING CONTROLS. |
| | |
| | 3) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR |
| | EGRESS PATHS MEETING THE MINIMUM REQUIRED BY THE LIFE |
| | SAFETY CODE.THIS WAS REQUESTED ON PREVIOUS REVIEW AND |
| | THERE ARE SOME SEPARATE SHEETS SHOWING SOME LEVELS |
| | HOWEVER THE LEVELS SHOWN DO NOT MEET THE MINIMUM |
| | REQUIRED. |
| | PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ARE |
| | REQUIRED TO BE 10FT CANDLES UNDER NORMAL. THE SEPARATE |
| | SHEETS SHOW 7. |
| | PLEASE SEE THE EMERGENCY LEVELS ARE PERMITTED TO GO |
| | DOWN TO 1FT CANDLE. |
| | 7.9.2.1, 7.9.2.2 |
| | THE LEVELS SHALL BE SHOWN AND PART OF THE RECORD SETS |
| | OF PLANS. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-101 2003 AND FBC 1006.1.2 FOR |
| | CONTROLS IN EGRESS AREAS. PLANS SHOW A STANDARD SINGLE |
| | POLE SWITCH AT THE BOTTOM OF STAIRS AND NO CONTROLS ON |
| | STAIRS OR AT THE TOP OF THE STAIRS. |
| | PLEASE SEE COMMENT #2 ABOVE WITH RESPECT TO LIGHTING IN |
| | BUILDINGS REQUIRED TO BE TURNED OFF. |
| | PLEASE ADDRESS. |
| | |
| | 5) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT |
| | SUBMITTING LIGHTING PERFORMANCE CALCULATIONS AND MAKING |
| | SURE ALL LIGHTING ON PLANS COORDINATES WITH THE INPUT |
| | DATA REPORT WHICH IS PART OF THE ENERGY CALCULATIONS. |
| | PLEASE SEE NOW A METHOD *A* IS BEING SUBMITTED WHICH |
| | CAN NOT BE USED AT THIS TIME. METHOD *A* IS FOR A WHOLE |
| | BUILDING WITH ALL KNOWN COMPONENTS. AS THIS BUILDING |
| | CONTAINS AREAS WHICH ARE SHOWN FOR *FUTURE BUILD OUT* |
| | THE *A* MAY NOT BE USED. PLEASE SEE 13-400.3.B, |
| | 13-400.3.C, 13-101.1.6. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | |
| | ** THE SUBMITTED CALCULATIONS DO NOT COORDINATE WITH |
| | PLANS. |
| | SOME EXAMPLES OF THIS WILL BE NOTED BELOW HOWEVER THESE |
| | ARE ONLY SOME EXAMPLES AND IS NOT AN EXHAUSTED LIST. |
| | THE INPUT DATA REPORT WILL BE NOTED AS IDR. |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE SEE THE IDR WHICH SHOWS NO EXTERIOR LIGHTING. |
| | HOW IS THIS POSSIBLE WHEN THE PLANS MOST CERTAINLY |
| | CONTAIN SEVERAL EXTERIOR LIGHTING FIXTURES? |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE SEE THE IDR WHICH SHOWS ONE DOORS. HOW IS THIS |
| | POSSIBLE WHEN THE PLANS CERTAINLY CONTAIN DOORS FROM |
| | CONDITIONED SPACE TO UNCONDITIONED SPACE WHICH AS SHOWN |
| | EXCEED ONE? |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE KNOW IF A METHOD *A* COULD BE USED ALL LIGHTING |
| | INCLUDING GARAGE AREA WOULD BE REQUIRED TO BE SHOWN IN |
| | THE IDR> |
| | |
| | ** FOR EXAMPLE: |
| | PLEASE VERIFY SOME LIGHTING CONTROLS NOTED * WITH |
| | DAYLIGHT ON/OFF*. WHERE ARE THESE ON PLANS? |
| | |
| | ** FOR EXAMPLE: |
| | NOT ALL FIXTURES ON PLANS ARE COMPLETED, SOME SHOWN AS |
| | *J* BOX ONLY. |
| | |
| | ** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT AND |
| | ARE NOT ALL ITEMS. |
| | |
| | 6) NOTE: PLANS INDICATE SOME SORT OF TIMER SWITCH |
| | DEVICES YET AS THIS DEVICE IS NOT SPECIFIC AS NOTED |
| | ABOVE PLEASE SEE FBC 11-4.27 AND MORE SPECIFICALLY |
| | 11-4.27.4 FOR TIME TYPE DEVICES. |
| | |
| | 7) NOTE: PLEASE SHOW THE LOCATION OF THE PROPOSED |
| | SERVICE. 110.26, 240.4, 230.70, 230.71, 230.72 ETC |
| | FBC106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY. |
| | |
| | 8) NOTE: PLEASE SEE 645.10. THERE IS A SHUNT TRIP |
| | PUSHBUTTON ON POWER PLANS NOTED OUTSIDE *IT* ROOM YET |
| | THIS DOES NOT PROVIDE THE DISCONNECTING MEANS AS |
| | REQUIRED IN SECTION ABOVE. AS THERE ARE CIRCUITS FROM |
| | TWO SEPARATE SOURCES INCLUDING PANELS *A* AND *B* BOTH |
| | WOULD REQUIRE BREAKERS IN EACH CIRCUIT OR PANEL. AS THE |
| | PANELS DO NOT INDICATE ANY DEVICES FOR REQUIRED |
| | DISCONNECT THE SCENARIO AS SHOWN DOES NOT MEET THE |
| | CODE. |
| | WHERE IS THE REQUIRED DISCONNECT FOR A/C EQUIPMENT? |
| | PLEASE BE SURE TO LOOK AT THE SECTION OF THE CODE NOTED |
| | AND PROVIDE A DIAGRAM OR COMPLETE PLANS SHOWING |
| | COMPLIANCE. |
| | |
| | 9) NOTE: PLEASE COORDINATE ELECTRICAL PLANS WITH |
| | MECHANICAL PLANS FOR CONTROLS OF BATHROOM EXHAUST |
| | FANS. |
| | MECHANICAL CODE REQUIRES CONTROLS OTHER THAN THE SINGLE |
| | POLE SWITCH AS SHOWN ON ELECTRICAL PLANS. THIS IS A |
| | MECHANICAL CODE REQUIREMENT. |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION, |
| | COORDINATION AND CLARITY REQUIRES PLANS TO MATCH. |
| | FBC/MECHANICAL CODE 402.3.1 |
| | |
| | 10) NOTE:PLEASE VERIFY NEW OR EXISTING ROOF-TOP GFI |
| | FOR NEW IT ROOM UNIT .210.63, 210.8B |
| | |
| | 11) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE ACCESS |
| | CONTROL SYSTEM OR WILL THIS BE UNDER SEPARATE PLANS AND |
| | PERMIT. |
| | PLEASE SEE NFPA-101 7.2.1.5, 7.2.1.6.2 |
| | |
| | 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | ** PLEASE KNOW SOME ELECTRICAL PLANS AS WELL AS |
| | CALCULATIONS WERE RETAINED BY THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |