2008-07-03 12:04:08BUILDING PLAN REVIEW
 PERMIT: 08030500
 ADD: 915 N DIXIE HW
 CONT: GLACE & CO
 TEL: (561)585-5564
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A-1C) COMPLIED.
  
 1D ) FILED NOTICE OF COMMENCEMENT DATE 11-20-07 IS OUT
 OF DATE AND WILL NEED TO BE REFILLED.FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OF COMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 1E) COMPLIED.
  
 2-5)COMPLIED.
  
 6) BUILDING PROVISO; ELEVATORS AND CONVEYANCE SYSTEMS
 ARE BY DEFINITION 3001.6 AN ELEVATOR, DUMBWAAITER,
 ESCALATOR, MOVING SIDEWALK, PLATFORM LIFTS AND STAIRWAY
 LIFTS THAT ALL WILL NEED TO COMPLY WITH THE REFRENCED
 STANDARDS. PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS
 MEETING THE REFERENCED STANDARDS IN3001.2.THE
 DOCUMENTS SUBMITTED DO NOT INDICATE ANY OF THE
 REFERENCED STANDARDS LISTED UNDER THIS CODE SECTION.
  
 7) 2ND REQUEST, THE ORIGINAL SHEET A2.1 INDICATED USE
 OF A ENCLOSED PARKING GARAGE. THE RESUBMITTED PLANS
 INDICATE THIS SPACE TO BE FUTURE OFFICE. INDISCUSSING
 THIS ISSUE WITH ROBERT BROWN ASST BUILDING OFF. IF THE
 PLANS ARE GOING TO STATE FUTURE OFFICE THEN THE GARAGE
 ENTRY DOORS WOULD NEED TO BE REMOVED AND EITHER BLOCKED
 UP OR STOREFRONT INSTALLED TO SHOW INTENT OF A FUTURE
 OFFICE. THE OTHER ISSUE IS THAT YOUR PLANS WOULD NEED
 TO BE REVIEWED BY PALM BEACH COUNTY IMPACT FEE OFFICE
 FOR ADDITIONAL IMPACT FEE ASSESSMENT. SHEET A2.1
 INDICATES A WALL TYPE 11 THAT SEPERATES THE OFFICE AREA
 FROM AN ENCLOSED PARKING GARAGE. THIS WILL REQUIRE A
 2HR SEPERATION AS PER TABLE 302.3.2. WHERE AS THE WALL
 TYPE 11 IS INDICATED AS A INTERIOR NONRATED WALL.
 PLEASE INDICATE WHERE THE 2 HR FIRE RATED WALL WILL BE.
 ALSO OPENING PROTECTION TABLE 715.3.
  
 8) BUILDING PROVISO:NOTE CHAPTER 11 IS NOT ABOUT
 EGRESS REQUIREMENTS BUT ACCESSIBILITY. IF ENTRYS ARE
 NOT ACCESSIBLE THEN SIGNAGE IS REQUIRED INDICATING
 WHERE THE ACCESSIBLE ENTRY WOULD BE AND SIGNAGE
 INDICATING THAT THIS IS NOT AN ACCESSIBLE DOORWAY. REAR
 OF BUILDING, DOOR 111D & 111E, THE DOOR SCHEDULE
 INDICATES EACH OF THESE DOORS AS A PAIR OF BI-PASS DOOR
 WITH A CLEAR OPENING OF 2'-6", 11-4.13.5 DOORWAY MIN
 CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM CLEAR WIDTH
 OF 32" WITH THE DOOR OPEN 90-DEGREES, MEASURED BETWEEN
 THE FACE OF THE DOOR AND OPPOSITE STOP.
  
 9) COMPLIED.
  
 10) CHANGE IN OCCUPANCY THE GARAGE TO OFFICE PORTION OF
 THE PLANS WILL REQUIRE REVIEW FROM PALM BEACH COUNTY
 IMPACT FEE OFFICE.
  
 11) NEW COMMENT IN THE RESTROOM 127 THE HANDICAPPED
 SHOWER NEEDS TO CONFORM WITH FIGURE 35A, THE 48 INCH
 CLEAR FLOOR SPACE REQUIRES 1'-0" PAST THE OPPOSITE WALL
 OF THE SEAT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 7-08-08
 COMMENT NUMBER 6 & 8 CAN AND WILL BOTH BE BUILDING
 PROVISOS: