| 2008-07-03 12:04:08 | BUILDING PLAN REVIEW |
| | PERMIT: 08030500 |
| | ADD: 915 N DIXIE HW |
| | CONT: GLACE & CO |
| | TEL: (561)585-5564 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1A-1C) COMPLIED. |
| | |
| | 1D ) FILED NOTICE OF COMMENCEMENT DATE 11-20-07 IS OUT |
| | OF DATE AND WILL NEED TO BE REFILLED.FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE |
| | NOTICE OF COMMENCEMENT IS NOT ACTUALLYCOMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE |
| | IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF THE |
| | NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE |
| | THE FIRST INSPECTION. |
| | |
| | 1E) COMPLIED. |
| | |
| | 2-5)COMPLIED. |
| | |
| | 6) BUILDING PROVISO; ELEVATORS AND CONVEYANCE SYSTEMS |
| | ARE BY DEFINITION 3001.6 AN ELEVATOR, DUMBWAAITER, |
| | ESCALATOR, MOVING SIDEWALK, PLATFORM LIFTS AND STAIRWAY |
| | LIFTS THAT ALL WILL NEED TO COMPLY WITH THE REFRENCED |
| | STANDARDS. PLEASE PROVIDE THE MANUFACTURERS CUT SHEETS |
| | MEETING THE REFERENCED STANDARDS IN3001.2.THE |
| | DOCUMENTS SUBMITTED DO NOT INDICATE ANY OF THE |
| | REFERENCED STANDARDS LISTED UNDER THIS CODE SECTION. |
| | |
| | 7) 2ND REQUEST, THE ORIGINAL SHEET A2.1 INDICATED USE |
| | OF A ENCLOSED PARKING GARAGE. THE RESUBMITTED PLANS |
| | INDICATE THIS SPACE TO BE FUTURE OFFICE. INDISCUSSING |
| | THIS ISSUE WITH ROBERT BROWN ASST BUILDING OFF. IF THE |
| | PLANS ARE GOING TO STATE FUTURE OFFICE THEN THE GARAGE |
| | ENTRY DOORS WOULD NEED TO BE REMOVED AND EITHER BLOCKED |
| | UP OR STOREFRONT INSTALLED TO SHOW INTENT OF A FUTURE |
| | OFFICE. THE OTHER ISSUE IS THAT YOUR PLANS WOULD NEED |
| | TO BE REVIEWED BY PALM BEACH COUNTY IMPACT FEE OFFICE |
| | FOR ADDITIONAL IMPACT FEE ASSESSMENT. SHEET A2.1 |
| | INDICATES A WALL TYPE 11 THAT SEPERATES THE OFFICE AREA |
| | FROM AN ENCLOSED PARKING GARAGE. THIS WILL REQUIRE A |
| | 2HR SEPERATION AS PER TABLE 302.3.2. WHERE AS THE WALL |
| | TYPE 11 IS INDICATED AS A INTERIOR NONRATED WALL. |
| | PLEASE INDICATE WHERE THE 2 HR FIRE RATED WALL WILL BE. |
| | ALSO OPENING PROTECTION TABLE 715.3. |
| | |
| | 8) BUILDING PROVISO:NOTE CHAPTER 11 IS NOT ABOUT |
| | EGRESS REQUIREMENTS BUT ACCESSIBILITY. IF ENTRYS ARE |
| | NOT ACCESSIBLE THEN SIGNAGE IS REQUIRED INDICATING |
| | WHERE THE ACCESSIBLE ENTRY WOULD BE AND SIGNAGE |
| | INDICATING THAT THIS IS NOT AN ACCESSIBLE DOORWAY. REAR |
| | OF BUILDING, DOOR 111D & 111E, THE DOOR SCHEDULE |
| | INDICATES EACH OF THESE DOORS AS A PAIR OF BI-PASS DOOR |
| | WITH A CLEAR OPENING OF 2'-6", 11-4.13.5 DOORWAY MIN |
| | CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM CLEAR WIDTH |
| | OF 32" WITH THE DOOR OPEN 90-DEGREES, MEASURED BETWEEN |
| | THE FACE OF THE DOOR AND OPPOSITE STOP. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) CHANGE IN OCCUPANCY THE GARAGE TO OFFICE PORTION OF |
| | THE PLANS WILL REQUIRE REVIEW FROM PALM BEACH COUNTY |
| | IMPACT FEE OFFICE. |
| | |
| | 11) NEW COMMENT IN THE RESTROOM 127 THE HANDICAPPED |
| | SHOWER NEEDS TO CONFORM WITH FIGURE 35A, THE 48 INCH |
| | CLEAR FLOOR SPACE REQUIRES 1'-0" PAST THE OPPOSITE WALL |
| | OF THE SEAT. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | 7-08-08 |
| | COMMENT NUMBER 6 & 8 CAN AND WILL BOTH BE BUILDING |
| | PROVISOS: |