Plan Review Notes
Plan Review Notes For Permit 08030500
Permit Number 08030500
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-16 17:52:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHTS A0, A2.1, A2.3 & A2.4 COMPASS "N" IS
 INCONSISTANT. SHT A0 SHOWS COMPASS "N" AT THE TOP OF
 THE SHEET AS DOES SHT A2.3. BUT SHTS A2.1, A2.2 & A2.4
 SHOW COMPASS "N" AT THE BOTTOM OF THE SHEET.PLEASE
 CORRELATE. SECTION 106.1.1.
  
 2. SHT A2.1 TOILET ROOMS 109 & 110 SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. SHOW
 THE CLEAR FLOOR SPACE FOR ALL FIXTURES. DOORS MAY NOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE. SHOW THE TURNING AREA IN EACH TOILET ROOM.
 (DETAILS 8 & 9 SHT A8.2 ARE NOT CODE COMPLIANT). SEE
 SECTION 11-4.1.3(11).
  
 3. SHT A2.1 SHOW THE CLEAR FLOOR SPACE FOR THE ELECTRIC
 WATER COOLER, (DRINKING FOUNTAIN), AND SHOWERS AS WELL
 AS THE W/C'S & LAVS IN ALL TOILET ROOM/BATHROOMS.
 SECTIONS 11-4.15.5, 11-4.16.2, 11-4.19.3 & 11-4.21.2
 (FIG 35A OR 35B). ALSO SHOW THE CLEAR FLOOR SPACE FOR
 THE KITCHEN SINK PER 11-4.24.5.
  
 4. SHT A2.1 SHOWERS SHALL BE ACESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.21 WITH ALL
 SUBSECTIONS. SHOWER SIZES SHALL COMPLY WITH SECTION
 11-4.21.2 AND ARE REQUIRED TO BE 36" X 36" FINISHED
 DIMENSIONS, FIGURE 11-35A OR 30" X 60" FIGURE 11-35B.
 PLEASE INDICATED SIZE OF SHOWER ON PLANS.
  
 5. SHT A8.1 DETAILS 1,3 & 5 SHOW COMPLIANCE WITH
 SECTION 11-4.16.5 FLUSH CONTROLS, 11-4.19.2 CLEARANCES
 & 11-4.19.5 FAUCETS.
  
 6. SHT A8.1 DETAIL 21 SHOW COMPLIANCE WITH SECTIONS
 11-4.24.4 SINK DEPTH & 11-4.24.7 FAUCETS.
  
 7. SHT P-2 TRAP PRIMERS SHALL BE INSTALLED FOR THE
 FLOOR DRAINS AT EACH WATER HEATER. SECTION 1002.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved