| Plan Review Notes For Permit 08030500 |
| Permit Number |
08030500 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-21 16:02:09 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR THE | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES) . | | | | | | 4.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIRS | | | GUARDRAILS/HANDRAILS. | | | | | | 5.IT IS INDICATED ON SHEET LS2.1 THAT THE BUSINESS | | | OCCUPANCY IS SPRINKLERED AND THE PARKING GARAGE IS NOT. | | | PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.HOW | | | WILL THE SPRINKLER SYSTEM BE MONITORED? | | | | | | 6.ON SHEET E2.1, WHAT IS THE REASONING FOR THE CARD | | | READER AS SHOWN IN THE REC ROOM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|