Plan Review Notes
Plan Review Notes For Permit 08030500
Permit Number 08030500
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-31 16:14:22** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE
 REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND
 SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE VERIFY IF THIS BUILDING CONTAINS AN
 EXISTING FIRE ALARM SYSTEM. IF SO, PLEASE SEE FBC
 11-4.28.1,.2 AND .3(4) WITH RESPECT TO MINIMUM DEVICE
 LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE. NEED TO
 SHOW ON THIS PLAN AT THIS TIME.
  
 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 4) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS. SOME DEVICES ARE
 SHOWN AND NOTED HOWEVER NO INFORMATION OR DETAIL WAS
 SUBMITTED ON THE NOTED LIGHTING CONTROL SYSTEM. THE
 PLANS MAKE NOTE OF OVER RIDES HOWEVER NO INFORMATION ON
 SYSTEM WAS SUBMITTED.
 PLEASE ALSO SEE THERE ARE NUMEROUS SWITCHES WHICH ARE
 SHOWN AS STANDARD SWITCHES IN WHICH SOME SORT OF
 AUTOMATED CONTROLS ARE REQUIRED.
 PLEASE SEE REDLINED PLANS AS MANY OF THESE ARE NOTED.
 ** AS THERE IS MUCH INFORMATION NOT SUBMITTED NOT ALL
 POSSIBLE COMMENTS CAN BE MADE AT THIS TIME.
  
 5) NOTE: PLEASE SEE 13-415.2., 13-415.2.ABC.1.1, .1.2
 AND .1.3. PLEASE SHOW MORE ON HOW LIGHTING PERFORMANCE
 LEVELS WERE DERIVED.
 TABLE STATES 100 FIXTURES, HOWEVER BASED ON PLANS
 SUBMITTED AND MINIMUMS REQUIRED PER CODE SECTIONS GIVEN
 ABOVE THE LIGHTING ON PLANS IS NOT CODE COMPLIANT.
 BASED ON THE STATEMENT OF 100 FIXTURES ALONE,
 COMPLIANCE IS NOT MET. THERE MORE THAN 100 FIXTURES ON
 PLANS.
 PLEASE BE SURE TO GO OVER LIGHTING LEVELS AND SHOW
 COMPLIANCE WITH EITHER TABLE B OR C.
 PLEASE COORDINATE ALL LIGHTING WHICH WAS SUBMITTED ON
 THE ENERGY CALCULATIONS.
 FOR EXAMPLE: PLEASE SEE THE INPUT DATA REPORT WHICH
 DOES NOT SHOW ANY FIXTURES. HOW IS THIS POSSIBLE WHEN
 THE PLANS CONTAIN FIXTURES?
 THIS IS NOTED AS ONE EXAMPLE ONLY.
  
 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR
 LIGHTING. PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2. THE
 LIGHTING LEVELS UNDER NORMAL CONDITIONS ARE REQUIRED TO
 BE AT 10FT CANDLE MINIMUM AT ALL STAIRS LEVELS/WALKING
 SURFACES.
 PLEASE SEE LIGHTING IN STAIRS IS SHOWN BEING CONTROLLED
 BY A WALL MOUNTED OCCUPANCY SENSOR, HOWEVER THE
 COVERAGE FOR THIS DEVICE DOES NOT SEEM TO BE MET FOR
 LIFE SAFETY OR FOR COVERAGE REQUIRED FOR LIGHTING
 CONTROLS.
 PLEASE ALSO SEE FBC 1016 AND LS 101 7.8.1.2.2 WHICH
 REQUIRES ANY OCCUPANCY DEVICE FOR EGRESS TO BE A
 MINIMUM OF 15MINS AND ALSO FAIL-SAFE *ON*.
 PLEASE ADJUST PLANS, DEVICES, SUPPLY PHOTO-METRICS
 ETC.
 FAC 61G15-33.004
  
 7) NOTE: PLEASE COMPLETE ALL ROOM AND AREA DESIGNATIONS
 ON PLANS. PLEASE ALSO COMPLETE PANEL WITH CIRCUITING
 WHICH IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE WATER HEATER IS MISSING THE
 REQUIRED DISCONNECT PER 422.31
  
 9) NOTE: PLANS INDICATE A NEW SERVICE BEING INSTALLED
 ONLY FOR THIS TENANT.
 PLEASE SEE 230.2 AS A NEW SERVICE IS NOT GRANTED AT
 THIS TIME. PLEASE PROVIDE MORE INFORMATION ON VOLTAGE,
 SIZES OF EXISTING, NEW, LOCATIONS ETC.
 230.2, 230.70, 230.72, 110.9 ETC..
  
 ** AS NOTED ABOVE IN SOME OF THE COMMENTS, NOT ALL
 POSSIBLE REVIEW NOTES CAN BE MADE AT THIS TIME AS THERE
 IS SOME INFORMATION NOT YET SUBMITTED FOR REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-03-27 18:33:232008-03-27 18:33:23
  
 PLANS IN ELEC FOR REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved