| Date |
Text |
| 2008-03-31 16:14:22 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| | REQUIRED ON PLANS WHICH ARE RELEVANT TO DESIGN AND |
| | SCOPE OF WORK. |
| | 2004 FBC W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE VERIFY IF THIS BUILDING CONTAINS AN |
| | EXISTING FIRE ALARM SYSTEM. IF SO, PLEASE SEE FBC |
| | 11-4.28.1,.2 AND .3(4) WITH RESPECT TO MINIMUM DEVICE |
| | LOCATIONS AND DEVICE LEVELS FOR ADA COMPLIANCE. NEED TO |
| | SHOW ON THIS PLAN AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND |
| | PLACE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2,.1.3 AND |
| | .1.4 FOR MISSING LIGHTING CONTROLS. SOME DEVICES ARE |
| | SHOWN AND NOTED HOWEVER NO INFORMATION OR DETAIL WAS |
| | SUBMITTED ON THE NOTED LIGHTING CONTROL SYSTEM. THE |
| | PLANS MAKE NOTE OF OVER RIDES HOWEVER NO INFORMATION ON |
| | SYSTEM WAS SUBMITTED. |
| | PLEASE ALSO SEE THERE ARE NUMEROUS SWITCHES WHICH ARE |
| | SHOWN AS STANDARD SWITCHES IN WHICH SOME SORT OF |
| | AUTOMATED CONTROLS ARE REQUIRED. |
| | PLEASE SEE REDLINED PLANS AS MANY OF THESE ARE NOTED. |
| | ** AS THERE IS MUCH INFORMATION NOT SUBMITTED NOT ALL |
| | POSSIBLE COMMENTS CAN BE MADE AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.2., 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. PLEASE SHOW MORE ON HOW LIGHTING PERFORMANCE |
| | LEVELS WERE DERIVED. |
| | TABLE STATES 100 FIXTURES, HOWEVER BASED ON PLANS |
| | SUBMITTED AND MINIMUMS REQUIRED PER CODE SECTIONS GIVEN |
| | ABOVE THE LIGHTING ON PLANS IS NOT CODE COMPLIANT. |
| | BASED ON THE STATEMENT OF 100 FIXTURES ALONE, |
| | COMPLIANCE IS NOT MET. THERE MORE THAN 100 FIXTURES ON |
| | PLANS. |
| | PLEASE BE SURE TO GO OVER LIGHTING LEVELS AND SHOW |
| | COMPLIANCE WITH EITHER TABLE B OR C. |
| | PLEASE COORDINATE ALL LIGHTING WHICH WAS SUBMITTED ON |
| | THE ENERGY CALCULATIONS. |
| | FOR EXAMPLE: PLEASE SEE THE INPUT DATA REPORT WHICH |
| | DOES NOT SHOW ANY FIXTURES. HOW IS THIS POSSIBLE WHEN |
| | THE PLANS CONTAIN FIXTURES? |
| | THIS IS NOTED AS ONE EXAMPLE ONLY. |
| | |
| | 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR |
| | LIGHTING. PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2. THE |
| | LIGHTING LEVELS UNDER NORMAL CONDITIONS ARE REQUIRED TO |
| | BE AT 10FT CANDLE MINIMUM AT ALL STAIRS LEVELS/WALKING |
| | SURFACES. |
| | PLEASE SEE LIGHTING IN STAIRS IS SHOWN BEING CONTROLLED |
| | BY A WALL MOUNTED OCCUPANCY SENSOR, HOWEVER THE |
| | COVERAGE FOR THIS DEVICE DOES NOT SEEM TO BE MET FOR |
| | LIFE SAFETY OR FOR COVERAGE REQUIRED FOR LIGHTING |
| | CONTROLS. |
| | PLEASE ALSO SEE FBC 1016 AND LS 101 7.8.1.2.2 WHICH |
| | REQUIRES ANY OCCUPANCY DEVICE FOR EGRESS TO BE A |
| | MINIMUM OF 15MINS AND ALSO FAIL-SAFE *ON*. |
| | PLEASE ADJUST PLANS, DEVICES, SUPPLY PHOTO-METRICS |
| | ETC. |
| | FAC 61G15-33.004 |
| | |
| | 7) NOTE: PLEASE COMPLETE ALL ROOM AND AREA DESIGNATIONS |
| | ON PLANS. PLEASE ALSO COMPLETE PANEL WITH CIRCUITING |
| | WHICH IS SPECIFIC TO ROOMS AND AREAS IN WHICH THEY |
| | FEED. |
| | 408.4 |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE WATER HEATER IS MISSING THE |
| | REQUIRED DISCONNECT PER 422.31 |
| | |
| | 9) NOTE: PLANS INDICATE A NEW SERVICE BEING INSTALLED |
| | ONLY FOR THIS TENANT. |
| | PLEASE SEE 230.2 AS A NEW SERVICE IS NOT GRANTED AT |
| | THIS TIME. PLEASE PROVIDE MORE INFORMATION ON VOLTAGE, |
| | SIZES OF EXISTING, NEW, LOCATIONS ETC. |
| | 230.2, 230.70, 230.72, 110.9 ETC.. |
| | |
| | ** AS NOTED ABOVE IN SOME OF THE COMMENTS, NOT ALL |
| | POSSIBLE REVIEW NOTES CAN BE MADE AT THIS TIME AS THERE |
| | IS SOME INFORMATION NOT YET SUBMITTED FOR REVIEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-03-27 18:33:23 | 2008-03-27 18:33:23 |
| | |
| | PLANS IN ELEC FOR REVIEW |