| 2008-07-03 12:01:45 | |
| 2008-04-14 07:19:47 | BUILDING PLAN REVIEW |
| | PERMIT: 08030500 |
| | ADD: 915 N DIXIE HW |
| | CONT: GLACE & CO |
| | TEL: (561)585-5564 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) PLEASE SEE AERIAL VIEW,SEE ATTACHMENT. IT APPEARS |
| | THAT THE WORK IS TRANGRESSING THE PROPERTY LINE AND THE |
| | WRONG PROPERTY CONTROL NUMBER LISTED ON THE PERMIT |
| | APPLICATION. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE' |
| | SHALL BE |
| | RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE |
| | RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE |
| | 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | |
| | 3) PLEASE PROVIDE A SITE PLAN OF THE WHOLE BUIULDING |
| | SITE WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT. |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | THE LEVEL OF ALTERATION UNDER THE 2004 EXISTING |
| | BUILDING CODE. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F) |
| | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| | BUILDING PERMIT |
| | H) NUMBER OF FLOORS |
| | I ) SQ. FT. FOOTPRINT, FOOTPRINT |
| | |
| | 4) PLANS INDICATE A MEZZANINE, PLEASE PROVIDE AREA |
| | CALCULATIONS AS PER THE DEFINITION OF A MEZZANINE. |
| | 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A |
| | MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED |
| | ONE-THIRD OF THE AREA OF THAT ROOM OR SPACE IN WHICH |
| | THEY ARE LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL |
| | NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE |
| | ROOM IN WHICH THE MEZZANINE IS LOCATED. IN DETERMINING |
| | THE ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE |
| | SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. PLEASE |
| | INDICATE WHAT AREAS OFT THE MEZZANINE ARE COMMUNICATING |
| | WITH OTHER ROOMS. |
| | |
| | 5) ADDITIONAL INFORMATION REQUIRED, THE ELECTRICAL |
| | REVIEWERS COMMENET# 7IS NOT LIMITED TO BUT WILL |
| | INCLUDE THE IT ROOM FOUND ON SHEET A2.2. THIS ROOM IS |
| | NOT LISTED AS A IT ROOM ON E2.2. |
| | IF THIS IS A TRUE USE IT ROOM THIS COMMENT WILL APPEAR |
| | UNDER THE ELECTRICAL REVIEWERS COMMENTS NEXT REVIEW. IT |
| | ROOMS ARE REQUIRED BY NFPA 645.1-4 TO HAVE CERTAIN |
| | RATINGS. ONE THAT WILL PERTAIN TO BUILDING IS RATED |
| | WALLS, OPENING PROTECTION AND THROUGH WALL PENETRATIONS |
| | AND HORIZONTAL PENETRATIONS, TABLE 715.3, 712.3.1 & |
| | 712.4.1.PLEASE PROVIDE ADDITIONAL INFORMATION |
| | ACCORDINGLY. |
| | THANK YOU. |
| | |
| | 6) PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| | ELEVATOR, MINIMUM CAR PLAN DIMENSIONS, |
| | 11-4.1.6(2)(3)(C) ELEVATORS (I)-(III). |
| | |
| | 7)SHEET A2.1 INDICATES A WALL TYPE 11 THAT SEPERATES |
| | THE OFFICE AREA FROM AN ENCLOSED PARKING GARAGE. THIS |
| | WILL REQUIRE A 2HR SEPERATION AS PER TABLE 302.3.2. |
| | WHERE AS THE WALL TYPE 11 IS INDICATED AS A INTERIOR |
| | NONRATED WALL. PLEASE INDICATE WHERE THE 2 HR FIRE |
| | RATED WALL WILL BE. ALSO OPENING PROTECTION TABLE |
| | 715.3. |
| | |
| | 8) REAR OF BUILDING, DOOR 111D & 111E, THE DOOR |
| | SCHEDULE INDICATES EACH OF THESE DOORS AS A PAIR OF |
| | BI-PASS DOOR WITH A CLEAR OPENING OF 2'-6", 11-4.13.5 |
| | DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE A MINIMUM |
| | CLEAR WIDTH OF 32" WITH THE DOOR OPEN 90-DEGREES, |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND OPPOSITE |
| | STOP. |
| | |
| | 9) PLEASE PROVIDE INFORMATION WHY RESTROOMS 109 AND 110 |
| | ARE NOT ACCESSIBLE? IF EXISTING PLEASE PROVIDE |
| | CALCULATIONS FOR DISPROPORTIONATE COST11-4.1.6(2)(A). |
| | |
| | 10)IS THIS A CHANGE IN OCCUPANCY ENACTING IMPACT |
| | FEES?BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE.) |