| 2008-04-07 14:13:04 | 1. THE ENTIRE FIRE ALARM SYSTEM SHALL BE MONITORED BY A |
| | UL LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 2. AS NOTED ON THE PLANS, SMOKE DETECTORS SHALL BE |
| | INSTALLED A MINIMUM OF THREE FEET FROM AIR CONDITIONER |
| | DIFFUSERS. |
| | |
| | 3. SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT THE TOP |
| | OF THE ATRIUM ABOVE THE MONUMENTAL STAIR. A RECENT |
| | FIELD VISIT INDICATED THAT THE SMOKE DETECTORS LOCATED |
| | ON THE PERIMETER OF THE ATRIUM WOULD NOT ACTIVATE |
| | THEREFORE SMOKE DETECTION EQUIPMENT WILL BE NEEDED AT |
| | THE TOP. |
| | |
| | 4. TOTAL COMPLETE SMOKE DETECTION COVERAGE AS INDICATED |
| | IN CHAPTER 5, INITIATING DEVICES WITHIN NFPA 72, THE |
| | NATIONAL FIRE ALARM CODE "TOTAL COVERAGE SHALL INCLUDE |
| | ALL ROOMS, HALLS, STORAGE AREAS, BASEMENTS, ATTICS, |
| | LOFTS, SPACES ABOVE SUSPENDED CEILINGS AND OTHER |
| | SUBDIVISIONS AND ACCESSIBLE SPACES AS WELL AS THE |
| | INSIDE OF ALL CLOSETS, ELEVATOR SHAFTS, ENCLOSED |
| | STAIRWAYS, DUMBWAITER SHAFTS AND CHUTES". |
| | |
| | 5. SMOKE DETECTORS THAT ARE INSTALLED SHALL BE |
| | INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE |
| | ALARM CODE AND THE MANUFACTURER'S SPECIFICATIONS. |
| | |
| | 6. ANY FIRE ALARM DEVICE THAT IS SUBJECT TO MOISTURE |
| | INTRUSION SHALL BE INSTALLED IN A WEATHERPROOF MANNER |
| | TO PREVENT DAMAGE. |
| | |
| | 7. THE ENTIRE FIRE ALARM SYSTEM IS SUBJECT TO FIELD |
| | INSPECTION AND APPROVAL. |
| | |
| | APPROVED PROVISO: |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 |