| Date |
Text |
| 2008-04-16 14:50:25 | *****DENIED***** |
| | |
| | |
| | 1.ON SHEET A1-0 - GENERAL NOTE 18 - REFERENCES THE |
| | 2006 EDITION OF NFPA 101;AMEND TO SHOW 2003 EDITION |
| | AS CORRECTLY LISTED UNDER CODES. |
| | |
| | 2.VERIFY WITH THE PERMIT SPECIALIST THAT THE |
| | APPROPIATE UNIT OR UNITS IS/ARE REFLECTED IN THE |
| | PROJECT SITE ADDRESS.PRESENTLY, NO UNIT/UNITS IS/ARE |
| | SHOWN WHEN THE APPLIED PERMIT NUMBER IS ENTERED INTO |
| | COMMUNITY PLUS. |
| | |
| | 3.ON THE PERMIT APPLICATION, IT IS INDICATED THAT THE |
| | SCOPE OF WORK IS FOR UNITS G & H OF THE 900 BUILDING; |
| | HOWEVER ONLY UNIT "H" IS LISTED IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET.IN THE GENERAL NOTES UNDER |
| | THE WALL TYPE LEGEND, UNIT "G" IS LISTED. |
| | |
| | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 5.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR |
| | VICINITY THEREOF (INCLUDING ROADS, ALLEYS, FIRE |
| | LANES). |
| | |
| | 6.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 7.SMOKE DETECTORS OR SMOKE ALARMS?ON SHEET E1-0, |
| | SMOKE DETECTORS (SD) ARE SHOWN IN THE ELECTRICAL LEGEND |
| | AS WELL AS THE ELECTRICAL PLAN LAYOUT.PLEASE BE |
| | ADVISED THAT SMOKE DETECTORS (SD) ARE TIED INTO THE |
| | BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS (SA) |
| | SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT AND SHALL |
| | NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM. |
| | |
| | 8.SHOW THE LOCATION OF THE 2A10BC RATED FIRE |
| | EXTINGUISHERS WHICH SATISFIES THE 75' TRAVEL DISTANCE. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH ITEM WAS ADDRESSED |
| | |
| | |