| 2008-03-21 16:39:07 | ** DENIEDREVIEW ** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE FOLLOWING CODE IS IN AFFECT |
| | FOR THE ELECTRICAL CODE. |
| | 2005 NFPA-70 |
| | THIS IS REFLECTED ON COVER SHEET HOWEVER SEVERAL OF THE |
| | CODE SECTIONS NOTED ON ELECTRICAL PLANS ARE ACTUALLY |
| | NOT FROM THE CURRENT NEC. |
| | FOR EXAMPLE: PLEASE SEE PLANS REFLECT 220.19A, 220.30 |
| | ETC WHICH ARE NOT IN THE CURRENT CODE. |
| | PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN THE |
| | FOLLOWING CODES REFERENCE FOR DESIGN. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2004 FBC W/ 2007 REVISIONS. |
| | |
| | 2) NOTE: PLEASE SEE THE CONDUCTORS SHOWN FOR FEEDERS |
| | ARE NOT RATED FOR THE 125AMP MCB ON PANEL. |
| | PLEASE SHOW THE OVER CURRENT PROTECTION WHICH FEEDS |
| | THESE CONDUCTORS AT METER/SERVICE MAIN LOCATION. |
| | 310.16, 310.15B6, 240.6, 240.4 ETC |
| | |
| | 3) NOTE: PLEASE VERIFY IF PANEL IS GOING TO BE NEW OR |
| | ALREADY EXISTS. PLEASE SEE RISER WHICH NOTES THIS PANEL |
| | AS NEW YET THE PANEL SCHEDULE SHOW THIS AS EXISTING? |
| | FBC 106.1.2 FOR COORDINATION AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS |
| | CLEARLY STATE AND SHOW *SMOKE DETECTORS*. SMOKE |
| | DETECTORS ARE ONLY DEVICE WHICH DETECT AND DO NOT SOUND |
| | AN ALARM. THIS WOULD REQUIRE DEVICES TO BE PART OF HORN |
| | DEVICES AND A FIRE ALARM SYSTEM WHICH IS NOT SHOWN ON |
| | PLANS. |
| | SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND AN |
| | ALARM. |
| | PLEASE ADJUST ACCORDINGLY. |
| | 11.5.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, AND 220.52 AS |
| | THE DINING ROOM RECEPTACLES ARE NOT PERMITTED TO BE |
| | PART OF THE LIGHTING CIRCUIT WHICH IS WHAT IS NOTED ON |
| | PANEL SCHEDULE AND SHOWN ON PLANS. |
| | PLEASE ADJUST CIRCUITING, PLEASE ADJUST LOADS AND LOAD |
| | CALCULATIONS. |
| | PLEASE SEE SECTIONS AS NOTED. |
| | |
| | 6) NOTE: PLEASE SEE 210.11C3 AS THE BATH CIRCUITS SHALL |
| | BE DEDICATED TO EACH BATH ROOM OR ONLY THE RECEPTACLES |
| | MAY BE FED TO OTHER BATH ROOMS. |
| | IN EITHER CASE THESE MAY NOT FEED OTHER RECEPTACLES OR |
| | LOCATIONS. |
| | FOR EXAMPLE: BOTH BATH ROOMS ARE FED FROM THE SAME |
| | CIRCUIT AND ALSO PLANS SHOW THIS SAME CIRCUIT FEEDING |
| | OUTSIDE GFI. |
| | ALL OF THESE AS SHOWN ARE NOT PERMITTED. |
| | |
| | 7) NOTE: PLEASE LIST THE REQUIRED ARC FAULT CIRCUITS |
| | PER 210.12. THE PLANS DO NOTE PROTECTION IS REQUIRED |
| | HOWEVER THE CIRCUITS ON PANEL NEED TO SHOW THIS. |
| | |
| | 8) NOTE: PLEASE SEE 408.4 AS THIS REQUIRES THE PANEL |
| | SCHEDULE TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. |
| | |
| | 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| | CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FS |
| | 471.025, FAC 61G15-23.002 AND FBC 13-103.1.1.1. THE |
| | SHEETS IN FACT CONTAIN A RAISED SEAL OVER A |
| | *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED. |
| | |
| | 10) NOTE: PLEASE VERIFY SCOPE OF WORK AS PERMIT |
| | APPLICATION STATES UNIT G AND H YET PLANS ARE ONLY FOR |
| | UNIT H. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |