Plan Review Notes For Permit 08030477
Permit Number 08030477
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-21 16:39:07** DENIEDREVIEW **
  
  
  
 1) NOTE:PLEASE SEE THE FOLLOWING CODE IS IN AFFECT
 FOR THE ELECTRICAL CODE.
 2005 NFPA-70
 THIS IS REFLECTED ON COVER SHEET HOWEVER SEVERAL OF THE
 CODE SECTIONS NOTED ON ELECTRICAL PLANS ARE ACTUALLY
 NOT FROM THE CURRENT NEC.
 FOR EXAMPLE: PLEASE SEE PLANS REFLECT 220.19A, 220.30
 ETC WHICH ARE NOT IN THE CURRENT CODE.
 PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN THE
 FOLLOWING CODES REFERENCE FOR DESIGN.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC W/ 2007 REVISIONS.
  
 2) NOTE: PLEASE SEE THE CONDUCTORS SHOWN FOR FEEDERS
 ARE NOT RATED FOR THE 125AMP MCB ON PANEL.
 PLEASE SHOW THE OVER CURRENT PROTECTION WHICH FEEDS
 THESE CONDUCTORS AT METER/SERVICE MAIN LOCATION.
 310.16, 310.15B6, 240.6, 240.4 ETC
  
 3) NOTE: PLEASE VERIFY IF PANEL IS GOING TO BE NEW OR
 ALREADY EXISTS. PLEASE SEE RISER WHICH NOTES THIS PANEL
 AS NEW YET THE PANEL SCHEDULE SHOW THIS AS EXISTING?
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS
 CLEARLY STATE AND SHOW *SMOKE DETECTORS*. SMOKE
 DETECTORS ARE ONLY DEVICE WHICH DETECT AND DO NOT SOUND
 AN ALARM. THIS WOULD REQUIRE DEVICES TO BE PART OF HORN
 DEVICES AND A FIRE ALARM SYSTEM WHICH IS NOT SHOWN ON
 PLANS.
 SMOKE ALARMS ARE DEVICES WHICH DETECT AND SOUND AN
 ALARM.
 PLEASE ADJUST ACCORDINGLY.
 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SEE 210.52B1, 210.11C1, AND 220.52 AS
 THE DINING ROOM RECEPTACLES ARE NOT PERMITTED TO BE
 PART OF THE LIGHTING CIRCUIT WHICH IS WHAT IS NOTED ON
 PANEL SCHEDULE AND SHOWN ON PLANS.
 PLEASE ADJUST CIRCUITING, PLEASE ADJUST LOADS AND LOAD
 CALCULATIONS.
 PLEASE SEE SECTIONS AS NOTED.
  
 6) NOTE: PLEASE SEE 210.11C3 AS THE BATH CIRCUITS SHALL
 BE DEDICATED TO EACH BATH ROOM OR ONLY THE RECEPTACLES
 MAY BE FED TO OTHER BATH ROOMS.
 IN EITHER CASE THESE MAY NOT FEED OTHER RECEPTACLES OR
 LOCATIONS.
 FOR EXAMPLE: BOTH BATH ROOMS ARE FED FROM THE SAME
 CIRCUIT AND ALSO PLANS SHOW THIS SAME CIRCUIT FEEDING
 OUTSIDE GFI.
 ALL OF THESE AS SHOWN ARE NOT PERMITTED.
  
 7) NOTE: PLEASE LIST THE REQUIRED ARC FAULT CIRCUITS
 PER 210.12. THE PLANS DO NOTE PROTECTION IS REQUIRED
 HOWEVER THE CIRCUITS ON PANEL NEED TO SHOW THIS.
  
 8) NOTE: PLEASE SEE 408.4 AS THIS REQUIRES THE PANEL
 SCHEDULE TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED.
  
 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FS
 471.025, FAC 61G15-23.002 AND FBC 13-103.1.1.1. THE
 SHEETS IN FACT CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED* SIGNATURE WHICH IS NOT PERMITTED.
  
 10) NOTE: PLEASE VERIFY SCOPE OF WORK AS PERMIT
 APPLICATION STATES UNIT G AND H YET PLANS ARE ONLY FOR
 UNIT H.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.