| Date |
Text |
| 2008-03-20 08:49:59 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2004 FBC AS AMENDED, CHAPTER |
| | 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, THE |
| | METER ENCLOSURE IS NOT ON THE PLAN. INDICATE IF THE |
| | RISER IS CORRECT SHOWING AN UNDERGROUND FEED TO THE |
| | EXISTING PANELS (TO CONFIRM COMPLIANCE WITH 230.70(A) |
| | (1)). |
| | |
| | 2) THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. 250.6 |
| | 2005 NEC. |
| | NOTE: |
| | IT IS SHOWN AS AN EXISTING SERVICE BUT MUST BE |
| | CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE IS A |
| | POTENTIAL OF ENERGIZING ALL METAL PARTS AND EQUIPMENT |
| | THE EQUIPMENT GROUNDS ARE CONNECTED TO. |
| | |
| | 3} THE GROUNDING ELECTRODE CONDUCTOR IS SHOWN AS A |
| | #1/0, A #2 IS ALL THAT'S REQUIRED PER 250.66. PER |
| | 250.104(A) (1) THE COLD WATER BOND MUST BE SIZED PER |
| | 250.66, THEREFORE A #2 CU IS REQUIRED. FIELD VERIFY ALL |
| | CONDITIONS SHOWN ON THE RISER. |
| | NOTE: THE IMPLICATION THAT THE TRANSFER SWITCH WILL BE |
| | IN A REMOTE LOCATION FROM THE PANELS, SHOWN WITH MAIN |
| | BREAKERS WITH NO MAIN DISCONNECT AT THE METER, THIS |
| | COULD BE A VIOLATION OF 230.72(A), 2005 NEC. |
| | |
| | 4} THERE IS A STAIRWELL WITH A PARTITION BEING SHOWN TO |
| | BE REMOVED AT THE LANDING. SHOW WORK BEING DONE IN THAT |
| | AREA SO THE REQUIRED ELECTRICAL ISSUES MAY BE |
| | REVIEWED. |
| | |
| | 5} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC, |
| | 106.3.5.4 FBC AS AMENDED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |