Plan Review Notes
Plan Review Notes For Permit 08030391
Permit Number 08030391
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-29 11:23:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM,
 FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE
 SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL
 SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO
 REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE
 CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN
 AS NEW.
  
 THIS WAS ADDED TO A1.0; PLEASE ALSO ADD TO ELECTRIC
 SHEET(S) AS NECESSARY.
  
 2-7.ADDRESSED.
  
 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC.
  
 AS DISCUSSED, THE FOOD PREPARATION AREA IS TO BE
 SEPARATED FROM THE GENERAL AREA (CUSTOMER AND HALLWAY
 LEADING TO BATHROOM) WITH WALLS/DOORS.
  
 9-10. ADDRESSED.
  
 11.AS DISCUSSED, THE CORRIDOR IS MOST LIKELY A 1 HOUR
 DOOR (AS IT MAY SERVE A LARGE RESTAURANT, ASSEMBLY
 OCCUPANCY).PLEASE NOTE THIS 1 HOUR REQUIREMENT AND
 ALSO THE STRUCTURAL COLUMN REQUIREMENT ON THE PLAN SO
 THAT FIRE RESISTIVE REQUIREMENTS FOR WALLS, COLUMNS,
 AND PENETRATIONS WILL BE MAINTAINED.
  
 12.ADDRESSED.
  