| 2008-04-29 11:23:57 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM, |
| | FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE |
| | SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL |
| | SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO |
| | REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE |
| | CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN |
| | AS NEW. |
| | |
| | THIS WAS ADDED TO A1.0; PLEASE ALSO ADD TO ELECTRIC |
| | SHEET(S) AS NECESSARY. |
| | |
| | 2-7.ADDRESSED. |
| | |
| | 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY |
| | INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR |
| | SERVICE TO THE PUBLIC. |
| | |
| | AS DISCUSSED, THE FOOD PREPARATION AREA IS TO BE |
| | SEPARATED FROM THE GENERAL AREA (CUSTOMER AND HALLWAY |
| | LEADING TO BATHROOM) WITH WALLS/DOORS. |
| | |
| | 9-10. ADDRESSED. |
| | |
| | 11.AS DISCUSSED, THE CORRIDOR IS MOST LIKELY A 1 HOUR |
| | DOOR (AS IT MAY SERVE A LARGE RESTAURANT, ASSEMBLY |
| | OCCUPANCY).PLEASE NOTE THIS 1 HOUR REQUIREMENT AND |
| | ALSO THE STRUCTURAL COLUMN REQUIREMENT ON THE PLAN SO |
| | THAT FIRE RESISTIVE REQUIREMENTS FOR WALLS, COLUMNS, |
| | AND PENETRATIONS WILL BE MAINTAINED. |
| | |
| | 12.ADDRESSED. |
| | |