| Plan Review Notes For Permit 08030391 |
| Permit Number |
08030391 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-24 12:33:11 | *****UNSAT***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.ON SHEET A0.0, MAXIMUM TRAVEL DISTANCE TO AN EXIT | | | (SPRINKLERED) OF 300' IS INCORRECT.AS PER 2003 NFPA | | | 101 (37.2.6.1 AND/OR 36.2.6.2), TRAVEL DISTANCE (IN A | | | SPRINKLERED BUILDING) SHALL NOT EXCEED 250 FEET. | | | | | | 4.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 5.NO EXIT LIGHT(S) SHOWN ON PLAN. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|