Plan Review Notes
Plan Review Notes For Permit 08030391
Permit Number 08030391
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-19 12:24:58** DENIED**
  
  
 ICE BERRY
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES ARE
 REFLECTED ON PLANS. THERE ARE CURRENTLY CODES NOTES
 WHICH ARE NOT ADOPTED IN THE STATE OF FLORIDA. FOR
 EXAMPLE: THE PLANS NOTE *BOCA* CODE WHICH IS THE
 BUILDING OFFICIALS CODE ADMINISTRATION. THIS OFFICE HAS
 NO RECORDS OF THE BOCA CODE EVER ADOPTED IN THIS
 JURISDICTION AND EVEN AT A STATE LEVEL BEFORE 2001 UBC<
 SBCCI AND BOCA WAS ADOPTED IN SECTIONS OR SOME PLACES
 ON THE STATE LEVEL.
 PLEASE SEE THAT THE BOCA CODES WERE MERGED INTO ICC
 SEVERAL YEARS AGO. (SEE NOTE #40 ON E-0)
 PLEASE BE SURE TO REFERENCE THE FOLLOWING ON ELECTRICAL
 AND ARCHITECTURAL SHEETS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** SOME OF THE ABOVE ARE CORRECT ON SHEET A0.0 BUT NOT
 ALL. NONE ARE ON ELECTRICAL.
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL TITLE BLOCKS ARE
 MISSING THE REQUIRED FIRM LICENSE NUMBER WHICH IS ALSO
 KNOWN AS A CERTIFICATE OF AUTHORIZATION NUMBER.
 FAC 61G1-16.004 AND FS 481.219
  
 3) NOTE: PLEASE SEE FBC 13-101.3.2 AS THIS PROJECT
 STATES A CHANGE IN OCCUPANCY EVEN STATED ON PERMIT
 APPLICATION.
 PLEASE SEE THE SECTION GIVEN AS ALL LIGHTING EVEN IF
 EXISTING ALONG WITH LIGHTING CONTROLS SHALL MEET 13-4,
 MORE SPECIFICALLY 13-415.1.ABC.1.1, .1.1, .1.3 AND
 .1.4.
 PLEASE ALSO SEE 13-415.2 FOR LIGHTING PERFORMANCE
 LEVELS.
  
 4) NOTE: PLEASE SEE CODE SECTION NOTED FOR CIRCUITING
 OF EMERGENCY/EXIT LIGHTS IS NOT UNDER THE CURRENT CODE.
 PLEASE SEE 2005 NEC WHICH IS 700.12F.
 THIS COULD HAVE RED-LINED HOWEVER AS PLANS ARE COMING
 BACK AND THIS IS A PRIVATE PROVIDER PROJECT, PLANS MAY
 NOT BE RED-LINED OR PROVISO.
  
 5) NOTE: PLEASE KNOW AS THERE ARE SOME ITEMS NOT
 SUBMITTED OR IN DESIGN FOR REVIEW, THERE MAY VERY WELL
 BE NEW COMMENTS OF THE FOLLOWING AUDIT OF PLANS WHICH
 CAN NOT POSSIBLY BE MADE AT THIS TIME.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  