Plan Review Notes
Plan Review Notes For Permit 08030391
Permit Number 08030391
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-24 10:49:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM,
 FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE
 SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL
 SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO
 REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE
 CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN
 AS NEW.
  
 2.APPLICABLE CODES STATE FBC2004 WITH WPB AMENDMENTS.
 PLEASE DECLARE GOVERNING CODE BASED ON APPLICATION
 DATE; IN THIS CASE, FBC 2004 WITH 2007
 SUPPLEMENTS/REVISIONS.NOTE THAT AMENDMENTS APPLY ONLY
 TO CHAPTER 1, ADMINISTRATION.OTHER (CODE)
 REVISIONS/SUPPLEMENTS GOVERN THROUGHOUT THE STATE.
  
 3.M1, A0.0, HAVE REVISIONS IN INK.AS THIS IS A
 PRIVATE PROVIDER PLAN, I HAVE NO WAY TO DETERMINE
 WHETHER OR NOT THE REVIEWER HAS SEEN THESE CHANGES.
 PLEASE INCORPORATE ALL CHANGES TO THE PLAN INTO THE
 PRINTED SET.
  
 4.MAXIMUM TRAVEL DISTANCE A0.0 IS SHOWN AS 300FT, SEE
 FBC TABLE 1015.1 AND REVISE TO BE CODE COMPLIANT.
  
 5.DOORS E3, E1 ARE SHOWN ON THE PLAN AND LABELED BUT
 I WAS UNABLE TO LOCATE A NOTE INDICATING WHETHER THE
 EXISTING WILL REMAIN OR IF THEY WILL BE REPLACED.IF
 REPLACING, PROVIDE PRODUCT APPROVAL FAC9B72, HAVE
 REVIEWED BY DESIGNER OF RECORD, AND DECLARE COMPONENTS
 AND CLADDING PRESSURES FBC1603.IF EXISTING WILL
 REMAIN, PLEASE NOTE ON THE PLAN.
  
 6.BUILDING TYPE III IS DECLARED.OTHER PLANS HAVE
 DECLARED THIS BUILDING AS NONCOMBUSTIBLE; PLEASE
 PROVIDE INFORMATION REGARDING HOW YOU DETERMINED THIS
 BUILDING TYPE.
  
 7.A0.0 DECLARES THIS BUILDING AS "PROTECTED".THIS
 IS LANGUAGE FROM FBC2001 AND IS NO LONGER USED IN
 FBC2004.PLEASE DECLARE TYPE A OR B, FBC TABLE 601.
  
 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC.
  
 9.PLEASE PROVIDE SPECIFICATIONS FOR THE FRP PANEL AS
 I WAS UNABLE TO LOCATE THE THE TYPE SPECIFIED ON THE
 INTERNET.
  
 10.CERTIFICATE OF AUTHORIZATION REQUIRED FOR ZIEL
 DESIGN GROUP.THIS NUMBER IS REQUIRED TO BE PRINTED ON
 EACH SHEET, FAC61G1-15.002,003.
  
 11.TWO TENANT SEPARATION WALLS ARE SHOWN.NO
 INFORMATION WAS PROVIDED REGARDING THE THIRD INTERIOR
 WALL, BUT A MECHANICAL PENETRATION IS SHOWN THROUGH
 THIS WALL.PLEASE CLARIFY FIRE RESISTANCE RATING
 REQUIREMENT.IF THE THIS IS NOT A TENANT SEPARATION
 WITH A FIRE RATED DOOR, INCLUDE THIS ADDITONAL SQUARE
 FOOT AREA AND INCLUDE IN OCCUPANT LOAD.
  
 12.SIGNAGE REQUIED, FBC712.5 ABOVE THE NEW CEILING
 ALONG THE TENANT SEPARATION WALLS.PLEASE NOTE THAT ON
 THE PLAN THAT SIGNAGE WILL BE ADDED IF REQUIRED.
  
  