| 2008-03-24 10:49:22 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.FIRE ALARM STROBE IS NOT SHOWN IN THE BATHROOM, |
| | FBC11-4.28, SHEETS A1.0, E0 (ALTHOUGH OTHER STROBES ARE |
| | SHOWN ON THE PLAN).THERE IS A NOTE THAT "ALL |
| | SPRINKLER AND FIRE STROBE LOCATIONS ARE EXISTING TO |
| | REMAIN".THIS LIFE SAFETY ITEM IS REQUIRED, PLEASE |
| | CLARIFY IF THIS IS EXISTING AND IF NOT, ADD TO THE PLAN |
| | AS NEW. |
| | |
| | 2.APPLICABLE CODES STATE FBC2004 WITH WPB AMENDMENTS. |
| | PLEASE DECLARE GOVERNING CODE BASED ON APPLICATION |
| | DATE; IN THIS CASE, FBC 2004 WITH 2007 |
| | SUPPLEMENTS/REVISIONS.NOTE THAT AMENDMENTS APPLY ONLY |
| | TO CHAPTER 1, ADMINISTRATION.OTHER (CODE) |
| | REVISIONS/SUPPLEMENTS GOVERN THROUGHOUT THE STATE. |
| | |
| | 3.M1, A0.0, HAVE REVISIONS IN INK.AS THIS IS A |
| | PRIVATE PROVIDER PLAN, I HAVE NO WAY TO DETERMINE |
| | WHETHER OR NOT THE REVIEWER HAS SEEN THESE CHANGES. |
| | PLEASE INCORPORATE ALL CHANGES TO THE PLAN INTO THE |
| | PRINTED SET. |
| | |
| | 4.MAXIMUM TRAVEL DISTANCE A0.0 IS SHOWN AS 300FT, SEE |
| | FBC TABLE 1015.1 AND REVISE TO BE CODE COMPLIANT. |
| | |
| | 5.DOORS E3, E1 ARE SHOWN ON THE PLAN AND LABELED BUT |
| | I WAS UNABLE TO LOCATE A NOTE INDICATING WHETHER THE |
| | EXISTING WILL REMAIN OR IF THEY WILL BE REPLACED.IF |
| | REPLACING, PROVIDE PRODUCT APPROVAL FAC9B72, HAVE |
| | REVIEWED BY DESIGNER OF RECORD, AND DECLARE COMPONENTS |
| | AND CLADDING PRESSURES FBC1603.IF EXISTING WILL |
| | REMAIN, PLEASE NOTE ON THE PLAN. |
| | |
| | 6.BUILDING TYPE III IS DECLARED.OTHER PLANS HAVE |
| | DECLARED THIS BUILDING AS NONCOMBUSTIBLE; PLEASE |
| | PROVIDE INFORMATION REGARDING HOW YOU DETERMINED THIS |
| | BUILDING TYPE. |
| | |
| | 7.A0.0 DECLARES THIS BUILDING AS "PROTECTED".THIS |
| | IS LANGUAGE FROM FBC2001 AND IS NO LONGER USED IN |
| | FBC2004.PLEASE DECLARE TYPE A OR B, FBC TABLE 601. |
| | |
| | 8.SEE FBC1210.5, TOILET ROOMS SHALL NOT OPEN DIRECTLY |
| | INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR |
| | SERVICE TO THE PUBLIC. |
| | |
| | 9.PLEASE PROVIDE SPECIFICATIONS FOR THE FRP PANEL AS |
| | I WAS UNABLE TO LOCATE THE THE TYPE SPECIFIED ON THE |
| | INTERNET. |
| | |
| | 10.CERTIFICATE OF AUTHORIZATION REQUIRED FOR ZIEL |
| | DESIGN GROUP.THIS NUMBER IS REQUIRED TO BE PRINTED ON |
| | EACH SHEET, FAC61G1-15.002,003. |
| | |
| | 11.TWO TENANT SEPARATION WALLS ARE SHOWN.NO |
| | INFORMATION WAS PROVIDED REGARDING THE THIRD INTERIOR |
| | WALL, BUT A MECHANICAL PENETRATION IS SHOWN THROUGH |
| | THIS WALL.PLEASE CLARIFY FIRE RESISTANCE RATING |
| | REQUIREMENT.IF THE THIS IS NOT A TENANT SEPARATION |
| | WITH A FIRE RATED DOOR, INCLUDE THIS ADDITONAL SQUARE |
| | FOOT AREA AND INCLUDE IN OCCUPANT LOAD. |
| | |
| | 12.SIGNAGE REQUIED, FBC712.5 ABOVE THE NEW CEILING |
| | ALONG THE TENANT SEPARATION WALLS.PLEASE NOTE THAT ON |
| | THE PLAN THAT SIGNAGE WILL BE ADDED IF REQUIRED. |
| | |
| | |