| Plan Review Notes For Permit 08030389 |
| Permit Number |
08030389 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-04 10:37:48 | 2004 FBC W/2007 REVISIONS | | | INSTALL BUFFER WALL AND FENCE | | | PLAN REVIEW | | | | | | DENIED BY BUILDING | | | | | | 1) ON SHEETS G1 AND C11 THE PLANS REFERENCE ACI 318-95. | | | THE 2004 FBC REFERENCES ACI 318-02. PLEASE REVISE. FBC | | | CHAPTER 35 | | | | | | 2) ON THE PLANS, SPECIFY ALL DIMENSIONS FOR THE | | | PRE-CAST POST FOUNDATION, INCLUDING THE THICKNESS. FBC | | | 106.1.1* CITY AMENDMENTS | | | | | | 3) ENGINEERED SHOP DRAWINGS WILL BE REQUIRED FOR THE | | | PRE-CAST POSTS AND PANELS. FBC 106.1.2* CITY AMENDMENTS | | | | | | | | | 4) SUBMIT WINDLOAD CALCULATIONS FOR THE WALL. FBC | | | 106.1.2* CITY AMENDMENTS | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|