| Plan Review Notes For Permit 08030385 |
| Permit Number |
08030385 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-19 07:40:05 | 2004 FBC W/2007 REVISIONS | | | REPLACE 5 WINDOWS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE LOCATION | | | AND SIZE OF THE WINDOWS. IDENTIFY THE SLEEPING ROOMS ON | | | THE PLANS. FBC 106.1.1* CITY AMENDMENTS | | | | | | 2) IF THE SLEEPING ROOM WINDOWS ARE REPLACED THEY CAN | | | NOT REDUCE THE CLEAR OPENING BY MORE THAN 5 PERCENT AND | | | CAN NOT MAKE THE EGRESS OPENING LESS SAFE THAN THE | | | EXISTING CONDITIONS. FBC EXISTING BUILDINGS SECTIONS | | | 501.2 AND 505.1. | | | | | | 3) THE FBC EXISTING BUILDING SECTION 507.3 REQUIRES | | | OPENING PROTECTION FOR REPLACED WINDOWS, WHEN MORE THAN | | | 25 PERCENT OF THE GLAZED AREA IN THE DWELLING IS | | | REPLACED. SUBMIT PROOF THAT THE GLAZED AREA BEING | | | REPLACED IS LESS THAN 25 PERCENT OR SUBMIT 2 COPIES OF | | | PRODUCT APPROVALS FOR THE STORM PANELS. | | | | | | 4) IN ADDITION TO THE PRODUCT APPROVALS FOR THE STORM | | | PANELS, SUBMIT 2 COPIES OF A KEY PLAN AND AN | | | INSTALLATION SCHEDULE FOR THE STORM PANELS. SPECIFY THE | | | MOUNT TYPE, FASTENER TYPE AND SPACING, EDGE DISTANCES, | | | SPANS, ETC. SEE THE ATTACHED SAMPLE FORM. FBC 106.1.2* | | | CITY AMENDMENTS | | | | | | 5) PART OF THE PRODUCT APPROVAL DRAWINGS THAT WERE | | | SUBMITTED FOR THE WINDOWS HAS BEEN CUT OFF. SUBMIT THE | | | COMPLETE DRAWINGS. DCA RULE 9B-72 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|