2008-04-07 09:35:45 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THIS COMMENT IS FROM THE PEVIOUS REVIEW:
  
 1} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE INCLUDING ALL LOADS TO BE ADDED UNDER THIS
 PERMIT. INDICATE THE SIZE OF THE EXISTING SERVICE.
  
 THE LOAD CALCULATION SUBMITTED WAS ONLY FOR THE POOL
 PANEL, NOT THE SERVICE AS REQUESTED. THE CALCULATION
 SUBMITTED FOR THE POOL SUB-PANEL STATES THAT IT IS TO
 BE RATED AT 100 AMPS. SHEET 2 OF 2 INDICATES A 50 AMP
 POOL PANEL. CORRELATE WITH THE DESIGNER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718