| Plan Review Notes For Permit 08030383 |
| Permit Number |
08030383 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-07 09:35:45 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | THIS COMMENT IS FROM THE PEVIOUS REVIEW: | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE INCLUDING ALL LOADS TO BE ADDED UNDER THIS | | | PERMIT. INDICATE THE SIZE OF THE EXISTING SERVICE. | | | | | | THE LOAD CALCULATION SUBMITTED WAS ONLY FOR THE POOL | | | PANEL, NOT THE SERVICE AS REQUESTED. THE CALCULATION | | | SUBMITTED FOR THE POOL SUB-PANEL STATES THAT IT IS TO | | | BE RATED AT 100 AMPS. SHEET 2 OF 2 INDICATES A 50 AMP | | | POOL PANEL. CORRELATE WITH THE DESIGNER OF RECORD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|