Plan Review Notes
Plan Review Notes For Permit 08030366
Permit Number 08030366
Review Stop M
Sequence Number 1
Notes
Date Text
2008-03-18 11:00:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR
 GRILLS AND DUCTS ON THE MECHANICAL PLAN, PER 2004 WPB
 AMEND. 106.3.5.4 (10).
  
 2) THE GAS CLOTHES DRYER IS IN A CONFINED SPACE PLEASE
 PROVIDE COMBUSTION AND MAKE-UP AIR, SEE 2004 FBC/FG
 304.1, 304.4, AND 304.5.1.
  
 3) SHOW ON THE MECHANICAL PLAN WERE THE CLOTHES DRYER
 EXHAUST WILL TERMINATE. THECLOTHES DRYER VENT MAY NOT
 TERMINATE NEAR THE A/C CONDENSER UNIT, SEE 2004 FBC/R
 M303.4.2.
  
 4) THE MANUFACTURE SPEC. SHEET SUBMITTED FOR THE
 CLOTHES DRYER IS FOR AN ELECTRIC UNIT, PLEASE CORRECT.
  
 5) THE GAS WATER HEATER IS IN A CONFINED SPACE WITH AN
 EXHAUST FAN PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR,
 SEE 2004 FBC/FG 304.1, 304.4, AND 304.5.1.
  
 6) THE GAS WATER HEATER MAY NOT BE LOCATED IN A STORAGE
 CLOSET, PLEASE DO NOT REFER TO THE UTILITY ROOM AS
 STORAGE ON THE PLANS, SEE 2004 FBC/FG 303.3.
  
 7) THE MANUFACTURE SPEC. SHEET SUBMITTED FOR THE
 OUTDOOR GAS FIREPLACE STATES TWO WALLS OF THE PORCH
 MUST BE SCREENED AND THE MINIMUM SCREEN ARE IS TO BE 64
 SQUARE FEET. THE OUTDOOR LIVING AREA DOES NOT MEET
 THESE REQUIREMENTS, PLEASE CORRECT.
  
 8) PLEASE BE ADVISED THE EXHAUST FROM THE FUTURE GAS
 GENERATOR MAY NOT BE WITHIN FIVE FEET OF ANY BUILDING
 OPENINGS, PER NFPA 37.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]