| 2008-03-18 11:00:56 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR |
| | GRILLS AND DUCTS ON THE MECHANICAL PLAN, PER 2004 WPB |
| | AMEND. 106.3.5.4 (10). |
| | |
| | 2) THE GAS CLOTHES DRYER IS IN A CONFINED SPACE PLEASE |
| | PROVIDE COMBUSTION AND MAKE-UP AIR, SEE 2004 FBC/FG |
| | 304.1, 304.4, AND 304.5.1. |
| | |
| | 3) SHOW ON THE MECHANICAL PLAN WERE THE CLOTHES DRYER |
| | EXHAUST WILL TERMINATE. THECLOTHES DRYER VENT MAY NOT |
| | TERMINATE NEAR THE A/C CONDENSER UNIT, SEE 2004 FBC/R |
| | M303.4.2. |
| | |
| | 4) THE MANUFACTURE SPEC. SHEET SUBMITTED FOR THE |
| | CLOTHES DRYER IS FOR AN ELECTRIC UNIT, PLEASE CORRECT. |
| | |
| | 5) THE GAS WATER HEATER IS IN A CONFINED SPACE WITH AN |
| | EXHAUST FAN PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR, |
| | SEE 2004 FBC/FG 304.1, 304.4, AND 304.5.1. |
| | |
| | 6) THE GAS WATER HEATER MAY NOT BE LOCATED IN A STORAGE |
| | CLOSET, PLEASE DO NOT REFER TO THE UTILITY ROOM AS |
| | STORAGE ON THE PLANS, SEE 2004 FBC/FG 303.3. |
| | |
| | 7) THE MANUFACTURE SPEC. SHEET SUBMITTED FOR THE |
| | OUTDOOR GAS FIREPLACE STATES TWO WALLS OF THE PORCH |
| | MUST BE SCREENED AND THE MINIMUM SCREEN ARE IS TO BE 64 |
| | SQUARE FEET. THE OUTDOOR LIVING AREA DOES NOT MEET |
| | THESE REQUIREMENTS, PLEASE CORRECT. |
| | |
| | 8) PLEASE BE ADVISED THE EXHAUST FROM THE FUTURE GAS |
| | GENERATOR MAY NOT BE WITHIN FIVE FEET OF ANY BUILDING |
| | OPENINGS, PER NFPA 37. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |