| 2008-03-20 12:06:34 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS |
| | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY |
| | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| | DESIGNED. |
| | |
| | 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| | |
| | 4} THE PANEL LOCATED IN THE "STORAGE" ROOM IS IN |
| | VIOLATION OF 240.24(D) AND 408.17, 2005 NEC. |
| | |
| | 5} THE DISCONNECTS FOR THE IRRIGATION & POOL PUMPS AND |
| | THE A/C UNIT MUST HAVE CLEARANCE PER 110.26. |
| | |
| | 6} THE MASTER BATH REQUIRES ANOTHER RECEPTACLE WITHIN |
| | 3' OF THE SECOND BASIN TO COMPLY WITH 210.52(D). |
| | |
| | 7} THE HEAT LOAD IN THE CALCULATION @ 10K DOES NOT |
| | CORRELATE WITH THE MECHANICAL SPEC'S ON M-1 @13K. |
| | |
| | 8} NOTE #11 AND THE SMOKE ALARM SYMBOLS ARE INCORRECT. |
| | SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | 9} NOTE #15 INDICATES THERE IS A SHEET E-2, WHICH HAS |
| | NOT BEEN SUBMITTED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |