Plan Review Notes
Plan Review Notes For Permit 08030366
Permit Number 08030366
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-20 12:06:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} THE PANEL LOCATED IN THE "STORAGE" ROOM IS IN
 VIOLATION OF 240.24(D) AND 408.17, 2005 NEC.
  
 5} THE DISCONNECTS FOR THE IRRIGATION & POOL PUMPS AND
 THE A/C UNIT MUST HAVE CLEARANCE PER 110.26.
  
 6} THE MASTER BATH REQUIRES ANOTHER RECEPTACLE WITHIN
 3' OF THE SECOND BASIN TO COMPLY WITH 210.52(D).
  
 7} THE HEAT LOAD IN THE CALCULATION @ 10K DOES NOT
 CORRELATE WITH THE MECHANICAL SPEC'S ON M-1 @13K.
  
 8} NOTE #11 AND THE SMOKE ALARM SYMBOLS ARE INCORRECT.
 SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1
 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID
 CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE
 LOCATIONS OF THE SOUNDING DEVICES.
  
 9} NOTE #15 INDICATES THERE IS A SHEET E-2, WHICH HAS
 NOT BEEN SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  