| Plan Review Notes For Permit 08030365 |
| Permit Number |
08030365 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-12-26 09:00:47 | ** REDLINED PLANS** | | | | | | 1) NOTE: THE TOTAL NUMBER OF FIXTURES ON PLANS FOR | | | RECESSED LIGHTS IS OVER AMOUNT ON TABLE HOWEVER THIS | | | DOES NOT EXCEED OVER ALL ALLOWANCES. | | | THE WALL SCONCE FIXTURES ARE NOT LISTED ON FIXTURE | | | LEGEND AND NEEDS TO BE VERIFIED. | | | THE LED FIXTURES ARE LISTED WITH A TOTAL OF 200W WHICH | | | NEED TO BE VERIFIED. | | | NO ALLOWANCE FOR PENDANT FIXTURE COULD BE LOCATED. A | | | NOTE FOR THIS TYPE OF FIXTURE MENTIONS ONLY ON DURING | | | MEDICAL PROCEDURES HOWEVER THESE ARE ALSO IN THE | | | CONFERENCE ROOM. BASED ON THE MAXIMUM WATTAGE TOTAL OF | | | 300 FOR ALL THREE FIXTURES THIS WOULD NOT BE OVER | | | ALLOWANCES IN TABLE 13-415.2.B AND ADDITIONAL PERMITTED | | | UNDER TABLE. | | | | | | |
|