| Date |
Text |
| 2008-10-28 10:49:36 | REVISION DENIED |
| | REFERENCE: FBC-2004 CHAPTER 1 |
| | FBC-2004 PLUMBING |
| | |
| | 1. SHT P-1 INDICATES REVISION #3 DATED 9-15-2008. OUR |
| | FILE SET OF PLANS HAS A REVISION #3 DATED 7-3-2008. THE |
| | REVISIONS SHALL BE IN SEQUENCE AND PREVIOUS REVISIONS |
| | SHALL NOT BE DELETED FROM THE REVISION INDEX/MATRIX. |
| | SECTION 106.1.3. PLEASE SHOW NEW REVISION AS REVISION |
| | #4 OR ABOVE AND SHOW THE PREVIOUS REVISION #3 IN |
| | REVISION INDEX. |
| | |
| | 2. SHT P-1 SANITARY RISER DIAGRAM, THE FOUR SINKS IN |
| | THE EXAM ROOM ARE NOT VENTED. SECTION 901.2.1. (AN AAV |
| | ON ONE SINK AT EACH SUMP WILL MEET THIS REQUIREMENT). |
| | |
| | 3. SHT P-1 THE FOUR SINKS SHALL DRAIN INTO THE SUMP NOT |
| | THE DISCHARGE LINE ON THE SANITARY RISER DIAGRAM. |
| | SECTION 712.1. SHOW THE SINKS DRAINING TO THE SUMP. |
| | |
| | 4. SHT P-1 SANITARY RISER DIAGRAM SHOWS SHUT OFF VALVES |
| | ON THE DISCHARGE SIDE OF THE CHECK VALVES. SECTION |
| | 712.2 REQUIRES A FULL OPEN VALVE. PLEASE INDICATE ON |
| | RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |