Plan Review Notes
Plan Review Notes For Permit 08030365
Permit Number 08030365
Review Stop P
Sequence Number 4
Notes
Date Text
2008-10-28 10:49:36REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
  
 1. SHT P-1 INDICATES REVISION #3 DATED 9-15-2008. OUR
 FILE SET OF PLANS HAS A REVISION #3 DATED 7-3-2008. THE
 REVISIONS SHALL BE IN SEQUENCE AND PREVIOUS REVISIONS
 SHALL NOT BE DELETED FROM THE REVISION INDEX/MATRIX.
 SECTION 106.1.3. PLEASE SHOW NEW REVISION AS REVISION
 #4 OR ABOVE AND SHOW THE PREVIOUS REVISION #3 IN
 REVISION INDEX.
  
 2. SHT P-1 SANITARY RISER DIAGRAM, THE FOUR SINKS IN
 THE EXAM ROOM ARE NOT VENTED. SECTION 901.2.1. (AN AAV
 ON ONE SINK AT EACH SUMP WILL MEET THIS REQUIREMENT).
  
 3. SHT P-1 THE FOUR SINKS SHALL DRAIN INTO THE SUMP NOT
 THE DISCHARGE LINE ON THE SANITARY RISER DIAGRAM.
 SECTION 712.1. SHOW THE SINKS DRAINING TO THE SUMP.
  
 4. SHT P-1 SANITARY RISER DIAGRAM SHOWS SHUT OFF VALVES
 ON THE DISCHARGE SIDE OF THE CHECK VALVES. SECTION
 712.2 REQUIRES A FULL OPEN VALVE. PLEASE INDICATE ON
 RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved